Schneider Electric
LV433278
1 / 1
Description
Active Mature
This Compact NSX100R is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 200kA rms at 415VAC 50/60Hz and 45kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 5.2 E trip unit, with 40A rating. Micrologic 5.2 E trip unit provides adjustable long time, short time and instantaneous protection. Micrologic 5.2 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX100R is part of Schneider Electric EcoStruxure Power architecture.- Country of Origin
- FR
- Part Number
- LV433278
- Tariff Code
- 85362010
- EAN
- 3606480479359
- UNSPSC
- 39121601
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 1 pc.In-StockUpdated at: 08-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Specifications
- Network Frequency
- 50/60 Hz
- Line Rated Current
- 40 A 40 °C
- Trip Unit Name
- MicroLogic 5.2 E
- Range Of Product
- ComPact NSX100...250
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Trip Unit Protection Functions
- LSI
- Network Type
- AC
- Protected Poles Description
- 4t || 3t + OSN || 3t || 3t + N/2
- Product Or Component Type
- circuit breaker
- Product Name
- ComPact NSX
- Range
- ComPact
- Control Type
- toggle
- Utilisation Category
- category A
- Mounting Mode
- fixed
- Breaking Capacity
- 200 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 200 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 200 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 80 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 65 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 45 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes EN/IEC 60947-2
- Poles Description
- 4P
- Breaking Capacity Code
- R 200 kA 415 V AC
- Neutral Position
- left
- Device Application
- distribution
- Device Short Name
- NSX100R
- Trip Unit Technology
- electronic
Contractual warranty
- Warranty
- 18 months
Complementary
- [Ics] Rated Service Breaking Capacity
- 200 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 200 kA 380/415 V AC 50/60 Hz IEC 60947-2 || 200 kA 440 V AC 50/60 Hz IEC 60947-2 || 80 kA 500 V AC 50/60 Hz IEC 60947-2 || 65 kA 525 V AC 50/60 Hz IEC 60947-2 || 45 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Height
- 161 mm
- Thermal Memory
- 20 minutes before and after tripping
- Earth-Leakage Protection
- without
- Mounting Support
- backplate
- Instantaneous Pick-Up Adjustment Range
- 1.5...15 x In
- Type Of Measurement
- energy meter
- Downside Connection
- front
- Number Of Slots
- 5
- Communication Of Data
- time-stamped histories and event tables || maintenance indicators || instantaneous and demand values || maximeters/minimeters || protection and alarm settings || power quality || energy metering || demand current and power
- Protection Type
- L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection
- Long Time Delay Adjustment Type
- adjustable
- Instantaneous Pick-Up Adjustment Type Ii
- adjustable
- Zone Selective Interlocking Zsi
- with
- Net Weight
- 2.4 kg
- [Tr] Long-Time Delay Adjustment Range
- 15-400 s 1.5 x Ir || 0.35-11 s 7.2 x Ir || 0.5-16 s 6 x Ir
- Electrical Durability
- 10000 cycles 690 V In || 20000 cycles 690 V In/2 || 30000 cycles 440 V In || 50000 cycles 440 V In/2
- Short-Time Delay Adjustment Type
- adjustable
- Neutral Protection Setting
- 0.5 x Ir 3t + N/2) || 1 x Ir 4t) || 1.6 x Ir 3t + OSN) || no protection 3t)
- Long Time Pick-Up Adjustment Type Ir
- adjustable 9 settings
- Long Time Pick-Up Adjustment Range
- 18...40 A
- Upside Connection
- front
- [Tsd] Short-Time Delay Adjustment Range
- 0-0.4 s
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz
- Trip Unit Rating
- 40-40 A 40 °C
- Local Signalling
- for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
- Mechanical Durability
- 50000 cycles
- [Isd] Short-Time Pick-Up Adjustment Range
- 1.5...10 x Ir
- Connection Pitch
- 35 mm
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Width
- 140 mm
- Display Type
- LCD display
- Depth
- 86 mm
- Short-Time Pick-Up Adjustment Type Isd
- adjustable 9 settings
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- EAC || Marine || CCC
- Ik Degree Of Protection
- IK07 IEC 62262
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 60947
- Ip Degree Of Protection
- IP40 conforming to IEC 60529
- Electrical Shock Protection Class
- class II
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -40-85 °C
- Relative Humidity
- 0-95 %
- Operating Altitude
- 0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
- Overvoltage Category
- class II
CAD Models
traceparts
Download