1 / 1
thumbnail

Description

Active Mature
TeSys H ultra compact direct starter, 3 poles, 6.5A/500V AC-53, for control and protection of 3-phase motors up to 3kW@400V (3HP@480V). The hybrid technology used for power contacts procures ultra compactness (22.5mm width) as well as an extended electrical durability up to 30 million cycles AC-53. It provides control for one direction of rotation, an adjustable motor current 1.5-6.5A, class 10A thermal overload protection with auto/manual/remote reset, phase loss and phase unbalanced protection, stall and jam motor protection. To be supplied with 110-230V AC, it provides logic inputs for ON/OFF motor running and remote reset after thermal tripping, 1C/O contact relay for fault indication, LED status on front face for indication of tripping and motor running. DIN rail mounting, spring terminals for control and power, it can be used for ambient temperatures from -25 to 70°C, without derating until 30°C. Multi standards certified (IEC, UL, CCC), Green Premium compliant (RoHS/REACh).
Country of Origin
DE
Part Number
LZ1H6X53FU
Tariff Code
85371098
EAN
3606485421162
UNSPSC
39121521
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

[Uc] Control Circuit Voltage
110...230 V AC 50/60 Hz
[Ue] Rated Operational Voltage
500 V AC
Thermal Protection Adjustment Range
1.5-9 A
Product Or Component Type
ultra-compact starter
Product Name
TeSys Hybrid
Thermal Overload Class
class 10A IEC 60947-4-2
Motor Power Kw
1.5 kW 220 V AC 0.65 || 1.5 kW 230 V AC 0.65 || 2.2 kW 380 V AC 0.65 || 3 kW 400 V AC 0.65 || 3 kW 415 V AC 0.65 || 3 kW 440 V AC 0.65 || 3 kW 500 V AC 0.65
Range
TeSys
Motor Starter Type
direct on line
[Ie] Rated Operational Current
6.5 A 500 V AC-53A || 9 A 500 V AC-51 || 4.5 A 500 V AC-53A mounting side by side || 6 A 500 V AC-51 mounting side by side
Poles Description
3P
Maximum Horse Power Rating
1 hp 200 V AC || 1.5 hp 230 V AC || 3 hp 460 V AC
Device Short Name
LZ1H

Complementary

Height
99 mm
Reset
manual || automatic reset || electrical reset
Standards
IEC 60947-4-2 || UL 60947-4-1
Mounting Support
DIN rail
Pollution Degree
2
Net Weight
212 g
[Uimp] Rated Impulse Withstand Voltage
4 kV
Connections - Terminals
spring clamp terminals 1 0.2-2.5 mm² rigid || spring clamp terminals 1 0.25-2.5 mm² flexible - with cable end || spring clamp terminals 1 0.2-2.5 mm² flexible - without cable end
Current Consumption
<= 4 mA 110...230 V AC
[Ui] Rated Insulation Voltage
500 V AC 50/60 Hz
Mounting Mode
by clips
Maximum Operating Rate
120 cyc/mn AC-51 50 % || 6 cyc/mn AC-53A 50 %
Auxiliary Contact Composition
1 C/O fault signalling
Control Circuit Voltage Limits
85...253 V AC
Certifications
CE || cULus
Width
22.5 mm
Depth
114.5 mm
Electrical Durability
30 Mcycles

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1509013EN
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI1509013EN
Eu Rohs Directive
Compliant

Environment

Ambient Air Temperature For Operation
-25-30 °C without derating || 30-70 °C with derating
Ambient Air Temperature For Storage
-40-80 °C
Protective Treatment
TC
Ip Degree Of Protection
IP20

CAD Models

traceparts
traceparts
Download