1 / 1
thumbnail

Description

Active Mature
The EM3500 series offer a three-phases DIN rail-mounted energy meters fitted for accurate cost allocation and sub-metering. EM35xx models are designed for use with Low Votage Current Transducers 1/3Volt or 1Volt output. Current input from 5A to 32000A, according to the LVCT configuration in the HMI, ANSI C12.20 0.2% accuracy, IEC 62053-22 class 0.2S. 2 pulse outputs to communicate active and reactive energy, and 1 normaly closed contact for alarm. Suitable for a 230V AC network, with a supply voltage range of 90V AC to 300V AC at 50Hz or 60Hz. Compliant with UL508, CSA 22.2 number 14-05 and EN 61010-1. Product dimensions are as follows: width 107 mm, depth 59 mm, height 91 mm.
Country of Origin
US
Part Number
METSEEM3502
EAN
39121106
UNSPSC
39121106
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Complementary

Network Frequency
60 Hz || 50 Hz
[Ue] Rated Operational Voltage
90...347 V AC 50/60 Hz between phase and neutral UL || 156...600 V AC 50/60 Hz between phases UL || 90...300 V AC 50/60 Hz between phase and neutral CE || 125...300 V DC
Output Voltage
30 V AC/DC
Standards
UL 508 || CSA C22.2 No 14-05 || IEC 61010-1
Number Of Outputs
2 pulse || 1 alarm output
Mounting Support
DIN rail
Power Consumption In Va
5-5 VA 347 V AC between phase and neutral) || 5-5 VA 600 V AC between phases)
Product Certifications
CE IEC 61010 || cULus UL 508
Type Of Measurement
active and reactive power total || active and reactive power per phase || apparent power total || apparent power per phase || power factor total || power factor per phase || peak demand power || current || voltage || frequency
Communication Service
total cumulated active energy || total cumulated energy
Ride-Through Time
100 ms 120 V AC
Display Digits
5
Tamperproof Of Settings
protected by access code
Measurement Current
5-32000 A
Information Displayed
status and alert || communication with system || input/output status || error || Tx activity || Rx activity || instant power per usage
Function Available
fixed or rolling block
Mounting Mode
clip-on || by screws
Local Signalling
Red LED threshold reached || Green flashing LED output signal
Power Consumption In W
3 W 300-300 V
Measurement Accuracy
power +/- 0.2 % || energy +/- 0.2 %
Technology Type
electronic
Poles Description
3P + N
Data Recording
energy consumption logs
Analogue Input Type
split core current transducer 0.333 V or 1 V
Display Type
Backlit LCD
Device Application
partial meter || sub billing
Accuracy Class
class 0.2S power IEC 62053-22 || class 0.2S energy IEC 62053-22 || class 0.2S power ANSI C12.20 || class 0.2S energy ANSI C12.20
Rated Voltage
90-347 V

Environment

Ambient Air Temperature For Operation
-30-70 °C
Height
91 mm
9 Mm Pitches
12
Color
dark grey
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
0-95 %
Width
107 mm
Depth
59 mm

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Eu Rohs Directive
Compliant with Exemptions

Specifications

Product Or Component Type
energy meter
Product Name
PowerLogic EM3500
Range
PowerLogic
Device Short Name
EM3502
Metering Type
demand power P, Q, S || peak demand power PM, QM, SM || current I1, I2, I3, Iavg || voltage U21, U32, U13, V1, V2, V3

Documents

Data Sheet

Download