- Network Frequency
- 60 Hz || 50 Hz
- Communication Port Support
- RS485
- Power Quality Analysis
- up to the 15th harmonic
- Height
- 95 mm
- Measurement Voltage
- 50-330 V AC 45...65 Hz direct || 50-330 V AC 45...65 Hz phase to neutral || 80-570 V AC 45...65 Hz direct || 80-570 V AC 45...65 Hz phase to phase || 570-999000 V AC 45...65 Hz with external VT
- Sampling Rate
- 32 samples/cycle
- Standards
- BS EN 61557-12 || IEC 61557-12 || EN 61557-12 || BS EN 61326-1 || IEC 61326-1 || EN 61326-1 || BS EN 62052-11 || IEC 62052-11 || EN 62052-11 || BS EN 62053-21 || IEC 62053-21 || EN 62053-21 || BS EN 62053-22 || IEC 62053-22 || EN 62052-22 || BS EN 62053-23 || IEC 62053-23 || EN 62052-23 || BS EN 61010-1 || EN 61010-1 || IEC 61010-1 || UL 61010-1 || BS EN 61010-2-30 || IEC 61010-2-30 || EN 61010-2-30 || UL 61010-2-30 || ANSI C12.20
- Memory Capacity
- 512 KB
- Number Of Outputs
- 2 digital (static)
- Type Of Measurement
- active and reactive power || apparent power || current || voltage || energy || power factor || frequency || total current harmonic distortion THD (I) || total voltage harmonic distortion THD (U)
- Communication Port Protocol
- Modbus 9.6...38.4 kbauds
- Frequency Measurement Range
- 45-65 Hz
- Power Consumption In Va
- 5 VA
- Display Resolution
- 128 x 96 pixels
- Product Certifications
- CE IEC 61010-1 safety) || CE EN 61557-12 power monitor) || CE EN/IEC 61326-1 EMC) || UKCA BS EN 61010-1 safety) || UKCA BS EN 61557-12 power monitor) || UKCA BS EN 61326-1 EMC) || cULus EN 61010-1 safety) || cULus UL 61010-1 safety) || EAC sub-meter) || RCM
- Number Of Inputs
- 2 digital 0...4 mA 11...40 V DC
- Net Weight
- 0.26 kg
- Depth
- 70 mm
- Measurement Current
- 0.02-1.2 A || 0.05-6 A
- Information Displayed
- tariff 4)
- [Us] Rated Supply Voltage
- 100...277 V AC 45...65 Hz || 173...480 V AC 45...65 Hz || 100...300 V DC
- Mounting Mode
- clip-on
- Measurement Accuracy
- current 0.3 % 0.5...6 A || current 0.5 % 0.1...1.2 A || voltage 0.3 % 50...330 V || voltage 0.3 % 80...570 V
- Mounting Support
- DIN rail
- Poles Description
- 3P || 3P + N || 1P + N
- Data Recording
- energy consumption logs || 15 alarms || power logs || time stamping || min/max of instantaneous values
- Line Rated Current
- 5 A || 1 A
- Analogue Input Type
- current 0...5 A || current 0...1 A
- Width
- 90 mm
- Display Type
- Backlit LCD
- Device Application
- multi-tariff || power monitoring || sub billing
- Accuracy Class
- class 0.5S active energy IEC 62053-22 || class 1 active energy IEC 62053-21 || class 2 reactive energy IEC 62053-23 || class C active energy EN 50470-3