- Safety Reliability Data
- MTTFd = 296.8 years || B10d = 270000
- Setting Accuracy Of Time Delay
- +/- 10 % of full scale 25 °C IEC 61812-1
- Height
- 90 mm
- Creepage Distance
- 4 kV/3 IEC 60664-1
- Maximum Delay Response
- 100 ms
- Control Type
- selector switch front panel
- Insulation Resistance
- 100 MOhm 500 V DC IEC 60664-1
- Maximum Power Consumption In W
- 0.6 W 24 V DC
- Maximum Switching Current
- 8 A AC/DC
- Contacts Material
- cadmium free
- Power Consumption In Va
- 0-32 VA 240 V AC
- Dielectric Strength
- 2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
- Marking
- CE
- Voltage Range
- 0.85...1.1 Us
- Reset Time
- 120 ms on de-energisation typical
- Operating Rate In Hz
- 10 Hz
- Net Weight
- 0.07 kg
- Mounting Position
- any position in relation to normal vertical mounting plane
- Voltage Drift
- +/- 0.2 %/V
- Maximum Switching Voltage
- 250 V AC
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- Functionality
- multifunction
- Contacts Type And Composition
- 1 C/O
- [Us] Rated Supply Voltage
- 24...240 V AC 50/60 Hz || 24 V DC
- Temperature Drift
- +/- 0.05 %/°C
- Local Signalling
- LED indicator on steady: relay energised, no timing in progress || LED indicator 80 % ON and 20 % OFF flashing: timing in progress || LED indicator 5 % ON and 95 % OFF pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L)
- Minimum Switching Current
- 10 mA 5 V DC
- Input Voltage
- 10 V
- Mounting Support
- 35 mm DIN rail conforming to IEC 60715
- Electrical Durability
- 100000 cycles resistive 8 A 250 V AC
- Mechanical Durability
- 10000000 cycles
- Compatibility Code
- RE17
- Breaking Capacity
- 2000 VA
- On-Load Factor
- 100 %
- Housing Material
- self-extinguishing
- Impulse Duration
- 100 ms with load in parallel typical || 30 ms typical
- Time Delay Type
- Ad, Ah, N, O, P, Pt, TI, Tt, W
- [Uimp] Rated Impulse Withstand Voltage
- 5 kV 1.2/50 µs
- Depth
- 72 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Supply Frequency
- 50...60 Hz +/- 5 %
- Repeat Accuracy
- +/- 0.5 % IEC 61812-1