- Maximum Switching Capacity
- 4000 VA AC || 448 W DC
- Safety Reliability Data
- B10d = 100000
- [Ue] Rated Operational Voltage
- 184...253 V AC 50/60 Hz
- Operating Rate
- <= 600 cycles/hour under load || <= 18000 cycles/hour no-load
- Torque Value
- 0.8 N.m || 7.0 lbf.in
- Protection Category
- RT I
- Test Levels
- level A group mounting
- Contacts Material
- silver alloy (AgNi)
- Net Weight
- 0.050 kg
- [Uimp] Rated Impulse Withstand Voltage
- 3.6 kV IEC 61000-4-5
- Maximum Switching Voltage
- 300 V DC IEC
- Average Resistance
- 32500 Ohm AC 20 °C +/- 15 %
- Device Presentation
- complete product
- Connections - Terminals
- connector, 1 x 0.25...1 x 2.5 mm² AWG 22...AWG 14) flexible with cable end || connector, 2 x 0.25...2 x 1 mm² AWG 22...AWG 17) flexible with cable end || connector, 1 x 0.5...1 x 2.5 mm² AWG 20...AWG 14) solid without cable end || connector, 2 x 0.5...2 x 1.5 mm² AWG 20...AWG 16) solid without cable end
- Switching Voltage
- 12 V
- Average Coil Consumption
- 0.75 VA AC
- [Ie] Rated Operational Current
- 16 A AC-1/DC-1) NO IEC || 8 A AC-1/DC-1) NC IEC
- Sale Per Indivisible Quantity
- 30
- [Ui] Rated Insulation Voltage
- 400 V IEC 60947
- Minimum Switching Current
- 10 mA
- Electrical Durability
- 70000 cycles, 16 A at 250 V, AC-1 NO || 70000 cycles, 8 A at 250 V, DC-1 NC
- Mechanical Durability
- 10000000 cycles
- Operating Position
- any position
- Operating Time
- 20 ms operating || 20 ms reset
- Load Current
- 16 A 250 V AC
- Drop-Out Voltage Threshold
- >= 0.15 Uc AC
- Minimum Switching Capacity
- 120 mW 10 mA, 12 V