- Contacts Usage
- standard contacts
- Height
- 47 mm
- Terminals Description Iso N°1
- (13-14)NO
- Short-Circuit Protection
- 10 A cartridge fuse gG IEC 60947-5-1
- Fixing Mode
- by screws
- Fixing Center
- 40 x 50 mm 1...6 mm thick panel)
- Contacts Material
- silver alloy (Ag/Ni)
- Positive Opening
- without
- [Ith] Conventional Free Air Thermal Current
- 10 A IEC 60947-5-1
- Net Weight
- 0.117 kg
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-1
- Device Presentation
- complete product
- Resistance To High Pressure Washer
- 7000000 Pa 55 °C 0.1 m
- Electrical Durability
- 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C
- Key Withdrawal Position
- in any position
- [Ui] Rated Insulation Voltage
- 600 V 3)IEC 60947-1
- [Ie] Rated Operational Current
- 3 A 240 V, AC-15, A600 IEC 60947-5-1 || 6 A 120 V, AC-15, A600 IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 IEC 60947-5-1
- Mechanical Durability
- 1000000 cycles
- Torque Value
- 0.14 N.m NO changing electrical state
- Electrical Reliability
- λ < 10exp(-6) 5 V 1 mA in clean environment IEC 60947-5-4 || λ < 10exp(-8) 17 V 5 mA in clean environment IEC 60947-5-4
- Width
- 36.6 mm
- Depth
- 100 mm
- Tightening Torque
- 0.8-1.2 N.m IEC 60947-1
- Shape Of Screw Head
- cross Philips no 1 || cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm
- Device Mounting
- built-in
- Type Of Keylock
- key 455