Schneider Electric

XB5AK134G5C0

1 / 5
thumbnail
thumbnail
thumbnail
thumbnail
thumbnail

Description

Active Mature
This illuminated selector switch provides a versatile and highly visible interface for controlling your machines. It is easily installed into standard 22mm cut-outs and connected to your control circuits with simple screw-clamp connections. It provides a clear help to set up your machines in various operating modes, even in darker rooms with clear visual feedback.
Country of Origin
FR
Part Number
XB5AK134G5C0
Tariff Code
85365080
EAN
3606489758738
UNSPSC
39122217
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Environment

Product Certifications
LROS (Lloyds register of shipping) || GL || UL || CSA || DNV || BV
Ik Degree Of Protection
IK05 IEC 50102
Ambient Air Temperature For Operation
-40-70 °C
Resistance To Electromagnetic Fields
10 V/m IEC 61000-4-3
Standards
IEC 60947-1 || IEC 60947-5-1 || JIS C8201-5-1 || CSA C22.2 No 14 || IEC 60947-5-4 || UL 508 || JIS C8201-1
Shock Resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 || 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Vibration Resistance
5 gn 2-500 Hz)IEC 60068-2-6
Ip Degree Of Protection
IP66 IEC 60529 || IP67 IEC 60529
Ambient Air Temperature For Storage
-40-70 °C
Nema Degree Of Protection
NEMA 13 || NEMA 4X
Resistance To Electrostatic Discharge
6 kV on contact (on metal parts) IEC 61000-4-2 || 8 kV in free air (in insulating parts) IEC 61000-4-2
Electrical Shock Protection Class
class II IEC 60536
Protective Treatment
TH
Resistance To Fast Transients
2 kV IEC 61000-4-4
Electromagnetic Emission
class B IEC 55011

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Important Information

Important Message
A change in appearance may be noted on the product but does not affect its use in terms of function and safety. This makes it compatible with our Universal LED blocks

Complementary

Contacts Usage
standard contacts
Height
42 mm
Terminals Description Iso N°1
(13-14)NO || (11-12)NC
Short-Circuit Protection
10 A cartridge fuse gG IEC 60947-5-1
Contacts Material
silver alloy (Ag/Ni)
Light Source
universal LED
Positive Opening
with IEC 60947-5-1 appendix K
[Ith] Conventional Free Air Thermal Current
10 A IEC 60947-5-1
Net Weight
0.516 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-1
Current Consumption
14 mA
Device Presentation
complete product
Resistance To High Pressure Washer
7000000 Pa 55 °C 0.1 m
Electrical Durability
1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C
Service Life
100000 h at rated voltage and 25 °C
Surge Withstand
1 kV IEC 61000-4-5
[Ui] Rated Insulation Voltage
600 V 3)IEC 60947-1
Signalling Type
steady
Operating Torque
0.14 N.m NO changing electrical state
[Ie] Rated Operational Current
3 A 240 V, AC-15, A600 IEC 60947-5-1 || 6 A 120 V, AC-15, A600 IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 IEC 60947-5-1
Supply Voltage Limits
100-132 V AC
Mechanical Durability
500000 cycles
Electrical Reliability
λ < 10exp(-6) 5 V 1 mA in clean environment IEC 60947-5-4 || λ < 10exp(-8) 17 V 5 mA in clean environment IEC 60947-5-4
Width
30 mm
Depth
70 mm
Tightening Torque
0.8-1.2 N.m IEC 60947-1
Shape Of Screw Head
cross Philips no 1 || cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm

Specifications

Range Of Product
Harmony XB5
Mounting Diameter
22 mm
Type Of Operator
stay put
Product Or Component Type
illuminated selector switch
Shape Of Signaling Unit Head
round
Head Type
standard
Connections - Terminals
screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1 || screw clamp terminals, >= 1 x 0.22 mm² without cable end IEC 60947-1
Contacts Type And Composition
1 NO + 1 NC
Sale Per Indivisible Quantity
1
Bezel Material
plastic colour plated grey
Contact Operation
slow-break
Operator Profile
red standard handle
Operator Position Information
3 positions +/- 45°
Device Short Name
XB5
[Us] Rated Supply Voltage
110...120 V AC 50/60 Hz
Bulb Base
integral LED