Square D
RM4JA31F
1 / 1
- Part Number
- RM4JA31F
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Main
- Commercial Status
- Commercialised
- Range of product
- Zelio Control
- Product or component type
- Industrial measurement and control relays
- Relay type
- Current measurement relay
- Relay name
- RM4J
- Relay monitored parameters
- Overcurrent or undercurrent detection
- Time delay type
- Adjustable 0.05...30 s
- Power consumption in VA
- 1.9...3.3 VA AC
- Measurement range
- 100...1000 mA current DC
- Measurement range
- 100...1000 mA current AC 50/60 Hz
- Measurement range
- 10...100 mA current DC
- Measurement range
- 10...100 mA current AC 50/60 Hz
- Measurement range
- 0.3...30 mA current DC
- Measurement range
- 0.3...30 mA current AC 50/60 Hz
- Contacts type and composition
- 2 C/O
Complementary
- [Us] rated supply voltage
- 110...130 V AC, 50/60 Hz +/- 5 %
- Control circuit voltage limits
- 0.85...1.1 Uc
- Output contacts
- 2 C/O
- Internal input resistance
- 1 Ohm
- Internal input resistance
- 10 Ohm
- Internal input resistance
- 33 Ohm
- Permissible continuous overload
- 0.05 A
- Permissible continuous overload
- 0.15 A
- Permissible continuous overload
- 1.5 A
- Permissible non repetitive overload
- 0.5 A
- Permissible non repetitive overload
- 0.2 A
- Permissible non repetitive overload
- 5 A
- Setting accuracy of the switching threshold
- +/-5 %
- Setting accuracy of time delay
- 10 P
- Hysteresis
- 5...30 % adjustable of current threshold setting
- Marking
- CE : EMC 89/336/EEC
- Marking
- CE : LVD 73/23/EEC
- Overvoltage category
- III conforming to IEC 60664-1
- [Ui] rated insulation voltage
- 500 V conforming to IEC
- Supply disconnection value
- > 0.1 Uc
- Operating position
- Any position without derating
- Connections - terminals
- Screw terminals 2 x 2.5 mm², flexible cable without cable end
- Connections - terminals
- Screw terminals 2 x 1.5 mm², flexible cable with cable end
- Tightening torque
- 5.31...9.73 lbf.in (0.6...1.1 N.m)
- Mechanical durability
- 30000000 cycles
- [Ith] conventional free air thermal current
- 8 A
- [Ie] rated operational current
- 0.3 A at 115 V DC-13 158 °F (70 °C) conforming to VDE 0660
- [Ie] rated operational current
- 0.3 A at 115 V DC-13 158 °F (70 °C) conforming to IEC 60947-5-1/1991
- [Ie] rated operational current
- 0.1 A at 250 V DC-13 158 °F (70 °C) conforming to VDE 0660
- [Ie] rated operational current
- 0.1 A at 250 V DC-13 158 °F (70 °C) conforming to IEC 60947-5-1/1991
- [Ie] rated operational current
- 3 A at 250 V AC-15 158 °F (70 °C) conforming to VDE 0660
- [Ie] rated operational current
- 3 A at 250 V AC-15 158 °F (70 °C) conforming to IEC 60947-5-1/1991
- [Ie] rated operational current
- 3 A at 24 V AC-15 158 °F (70 °C) conforming to VDE 0660
- [Ie] rated operational current
- 3 A at 24 V AC-15 158 °F (70 °C) conforming to IEC 60947-5-1/1991
- [Ie] rated operational current
- 3 A at 115 V AC-15 158 °F (70 °C) conforming to VDE 0660
- [Ie] rated operational current
- 3 A at 115 V AC-15 158 °F (70 °C) conforming to IEC 60947-5-1/1991
- [Ie] rated operational current
- 2 A at 24 V DC-13 158 °F (70 °C) conforming to VDE 0660
- [Ie] rated operational current
- 2 A at 24 V DC-13 158 °F (70 °C) conforming to IEC 60947-5-1/1991
- Switching capacity in mA
- 10 mA at 12 V
- Switching voltage
- 250 V AC
- Contacts material
- 90/10 silver nickel contacts
- Number of cables
- 2
- Width
- 0.91 in (23 mm)
- Height
- 3.07 in (78 mm)
- Depth
- 3.15 in (80 mm)
- Terminals description ISO n°1
- (15-16-18)OC
- Terminals description ISO n°1
- (25-26-28)OC
- Terminals description ISO n°1
- (A1-A2)CO
- Terminals description ISO n°1
- (C-B1-B2-B3)CO
- Output relay state
- Tripped if A measured > A set
- Output relay state
- Tripped if V measured > V set
- 9 mm pitches
- 2.5
- Product weight
- 0.38 lb(US) (0.172 kg)
Environment
- Electromagnetic compatibility
- Electrostatic discharge - test level 8 kV, level 3 - air discharge conforming to IEC 61000-4-2
- Electromagnetic compatibility
- Electrostatic discharge - test level 6 kV, level 3 - contact discharge conforming to IEC 61000-4-2
- Standards
- EN/IEC 60255-6
- Product certifications
- CSA
- Product certifications
- GL
- Product certifications
- UL
- Ambient air temperature for storage
- -40...185 °F (-40...85 °C)
- Ambient air temperature for operation
- -4...149 °F (-20...65 °C)
- Environmental characteristic
- 3K3
- Relative humidity
- 15...85 % conforming to IEC 60721-3-3
- Shock resistance
- 15 gn 11 ms conforming to IEC 60255-21-1
- IP degree of protection
- IP50 (casing) conforming to IEC 60529
- IP degree of protection
- IP20(terminals) conforming to IEC 60529
- Pollution degree
- 3 conforming to IEC 60664-1
- Dielectric test voltage
- 2.5 kV
- Non-dissipating shock wave
- 4.8 kV
- Resistance to electrostatic discharge
- 8 kV air conforming to IEC 61000-4-2 level 3
- Resistance to electrostatic discharge
- 6 kV contact conforming to IEC 61000-4-2 level 3
- Resistance to electromagnetic fields
- 9.14 V/yd (10 V/m) conforming to IEC 61000-4-3 level 3
- Resistance to fast transients
- 2 kV conforming to IEC 61000-4-4 level 3
- Protection against electric shocks
- 2 kV: level 3 conforming to IEC 61000-4-5
- Disturbance radiated/conducted
- CISPR 11 group 1 - class A
- Disturbance radiated/conducted
- CISPR 22 - class A
Ordering and Shipping Details
- Category
- 22376 - RELAYS-MEASUREMENT(RM4)
- Discount Schedule
- CP2
- GTIN
- 00785901481553
- Nbr. of units in pkg.
- 1
- Product availability
- Stock - Normally stocked in distribution facility
- Returnability
- Y
- Country of origin
- ID
Contractual Warranty
- Warranty period
- 18 months
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther