Main

Commercial Status
End of commercialisation
Range of product
Zelio Control
Product or component type
Industrial measurement and control relays
Relay type
Voltage control relay
Relay name
RM4U
Relay monitored parameters
Overvoltage and undervoltage detection
Relay monitored parameters
Self-powered
Time delay
Adjustable 0.1...10 s
Minimum switching current
10 mA at 12 V
Maximum switching current
8 A at 250 V AC
Electrical connection
2 conductors cable 0 in² (2.5 mm²) flexible cable without cable end conforming to IEC 60947-1
Electrical connection
2 conductors cable 0 in² (1.5 mm²) flexible cable with cable end conforming to IEC 60947-1
Contacts type and composition
2 C/O
Poles description
1P

Complementary

[Us] rated supply voltage
160...300 V AC
Supply voltage limits
160...300 V AC
Control threshold undervoltage
160...220 V 50/60 Hz
Control threshold overvoltage
220...300 V
Output contacts
2 C/O
Setting accuracy of the switching threshold
+/-3 %
Setting accuracy of time delay
10 P
Hysteresis
5 % fixed of de-energisation threshold
[Ue] rated operational voltage
>= 160 V
Marking
CE : EMC 89/336/EEC
Marking
CE : LVD 73/23/EEC
Overvoltage category
III conforming to IEC 60664-1
Insulation resistance
> 500 MOhm at 500 V DC conforming to IEC 60255-5
[Ui] rated insulation voltage
500 V conforming to IEC
Control circuit voltage limits
0.85...1.1 Uc
Supply frequency
50/60 Hz +/- 5 %
Supply disconnection value
> 0.1 Uc
Operating position
Any position without derating
Tightening torque
5.31...9.73 lbf.in (0.6...1.1 N.m)
Mechanical durability
30000000 cycles
[Ith] conventional free air thermal current
8 A
[Ie] rated operational current
0.3 A at 115 V DC-13 158 °F (70 °C) conforming to VDE 0660
[Ie] rated operational current
0.3 A at 115 V DC-13 158 °F (70 °C) conforming to IEC 60947-5-1
[Ie] rated operational current
0.1 A at 250 V DC-13 158 °F (70 °C) conforming to VDE 0660
[Ie] rated operational current
3 A at 250 V AC-15 158 °F (70 °C) conforming to VDE 0660
[Ie] rated operational current
3 A at 250 V AC-15 158 °F (70 °C) conforming to IEC 60947-5-1
[Ie] rated operational current
3 A at 24 V AC-15 158 °F (70 °C) conforming to VDE 0660
[Ie] rated operational current
3 A at 24 V AC-15 158 °F (70 °C) conforming to IEC 60947-5-1
[Ie] rated operational current
3 A at 115 V AC-15 158 °F (70 °C) conforming to VDE 0660
[Ie] rated operational current
3 A at 115 V AC-15 158 °F (70 °C) conforming to IEC 60947-5-1
[Ie] rated operational current
2 A at 24 V DC-13 158 °F (70 °C) conforming to VDE 0660
[Ie] rated operational current
2 A at 24 V DC-13 158 °F (70 °C) conforming to IEC 60947-5-1
Switching voltage
250 V AC
Contacts material
90/10 silver nickel contacts
Number of cables
2
Height
3.07 in (78 mm)
Width
0.89 in (22.5 mm)
Depth
3.15 in (80 mm)
Terminals description ISO n°1
(15-16-18)OC
Output relay state
Tripped, fault present
9 mm pitches
2.5
Product weight
0.24 lb(US) (0.11 kg)

Environment

Standards
EN/IEC 60255-6
Product certifications
CSA
Product certifications
GL
Product certifications
UL
Ambient air temperature for storage
-40...185 °F (-40...85 °C)
Ambient air temperature for operation
-4...149 °F (-20...65 °C)
Relative humidity
15...85 % 3K3 conforming to IEC 60721-3-3
Vibration resistance
0.35 mm (f = 10...55 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn 11 ms conforming to IEC 60068-2-27
IP degree of protection
IP50 (casing) conforming to IEC 60529
IP degree of protection
IP20(terminals) conforming to IEC 60529
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2.5 kV
Non-dissipating shock wave
4.8 kV
Resistance to electrostatic discharge
8 kV air conforming to IEC 61000-4-2 level 3
Resistance to electrostatic discharge
6 kV contact conforming to IEC 61000-4-2 level 3
Resistance to electromagnetic fields
9.14 V/yd (10 V/m) conforming to IEC 61000-4-3 level 3
Resistance to fast transients
2 kV conforming to IEC 61000-4-4 level 3
Protection against electric shocks
2 kV conforming to IEC 61000-4-5 level 3
Disturbance radiated/conducted
CISPR 11 group 1 - class A
Disturbance radiated/conducted
CISPR 22 - class A

Ordering and Shipping Details

Category
22376 - RELAYS-MEASUREMENT(RM4)
Discount Schedule
CP2
GTIN
00785901712251
Nbr. of units in pkg.
1
Product availability
Non-Stock - Not normally stocked in distribution facility
Returnability
N
Country of origin
ID

Contractual Warranty

Warranty period
18 months