Wago

2204-1406

1 / 1
thumbnail
Part Number
2204-1406
Tariff Code
85369010000
UPC
4066966268089
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
800 V
Rated impulse voltage (III/3)
8 kV
Rated current
32 A
Current at conductor cross-section (max.) mm²
41 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
6.2 mm / 0.244 inches
Height
78.7 mm / 3.098 inches
Depth from upper-edge of DIN-rail
32.9 mm / 1.295 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Yellow
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.238 MJ
Weight
11.302 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

Specifications

Product Group Code
0036

Commercial Data

Country of origin
DE
GTIN
4066966268089
Customs tariff number
85369010000

Ex Information

Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 18 ATEX 1006 U / IECEx: PTB 18.0013U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
550 V
Rated current (Ex e II)
31 A
Rated current (Ex e II) with jumper
30 A

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
30 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
30 A

Power Loss

Power loss, per pole (potential)
1.024 W
Rated current IN for specified power loss
32 A
Resistance value for specified, current-dependent power loss
0.001 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Push-button
Connectable conductor materials
Copper
Nominal cross-section
4 mm²
Solid conductor
0.5 … 6 mm² / 20 … 10 AWG
Solid conductor; push-in termination
1 … 6 mm² / 14 … 10 AWG
Fine-stranded conductor
0.5 … 6 mm² / 20 … 10 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 4 mm² / 20 … 12 AWG
Fine-stranded conductor; with ferrule; push-in termination
1.5 … 4 mm² / 18 … 12 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
11 … 13 mm / 0.43 … 0.51 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
30 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
30 A