- Communication
- Modbus (TCP, UDP)
- ETHERNET protocols
- HTTP(S) || BootP || DHCP || DNS || SNTP || FTP(S) || SNMP
- Baud rate
- 10/100 Mbit/s
- Transmission medium
- Twisted pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length
- Transmission performance
- Class D per EN 50173
- Number of modules per node (max.)
- 250
- Number of modules without a bus extension (max.)
- 64
- Input and output process image (fieldbus) max.
- 1020 words/1020 words
- Supply voltage (system)
- 24 VDC (-25 … +30 %); via pluggable connector
- Current consumption (5 V system supply)
- 350 mA
- Total current (system supply)
- 700 mA
- Input current (typ.) at nominal load (24 V)
- 280 mA
- Power supply efficiency (typ.) at nominal load (24 V)
- 90 %
- Isolation
- 500 V system/field
- Indicators