Wago

792-805

1 / 3
thumbnail
thumbnail
thumbnail
Part Number
792-805
Tariff Code
85363010900
UPC
4017332843737
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for data networks/MCR-technology
Class Code : EC000943
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Safety And Protection

Protection type
IP00; IP20 with end and intermediate plate

Environmental Requirements

Ambient temperature (operation)
-40 … +80 °C
Ambient temperature (storage)
-40 … +80 °C

Electrical Data

Nominal operating voltage
DC 5 V
Highest continuous voltage
AC 4.2 V / DC 6 V
Nominal current
0.1 A
Nominal discharge current (8/20 µs) (line)
5 kA
Nominal discharge current (8/20 µs) (total)
10 kA
Protection level (line/line) (cat. C2 at IN)
≤ 27 V
Protection level (line/protected ground) (cat. C2 at IN)
≤ 50 V
Protection level (line/line) (cat. C3 at IN)
≤ 14 V
Protection level (line/protected ground) (cat. C3 at IN)
≤ 14 V
Response time (line/line)
≤ 1 ns
Limit frequency (line/line)
250 MHz
Limit frequency (line/protected ground)
180 MHz
Impedance
1 Ω
Capacitance (line/line)
≤ 19 pF
Capacitance (line/protected ground)
≤ 16 pF

Connection Data

Connections (number)
5
Connection technology
CAGE CLAMP®
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Strip length
5 … 6 mm / 0.2 … 0.24 inches

Physical Data

Width
6 mm / 0.236 inches
Height from upper-edge of DIN-rail
56 mm / 2.205 inches
Depth
91 mm / 3.583 inches

Material Data

Fire load
0.000 MJ
Weight
38.000 g

Standards And Specifications

Standards/specifications
IEC 61643-21

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0021

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4017332843737
Customs tariff number
85363010900

Notes

Note
The coordination characteristics of the surge arrester provide information about its discharge capacity and protection capability.

Related products