ABB

1SDA071804R1

1 / 1
thumbnail

Description

C.BREAKER SACE EMAX2 E4.2V 3200 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/TOUCH-LI R 3200 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Part Number
1SDA071804R1
UPC
80156447565430
UNSPSC
39121615
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power circuit-breaker for trafo/generator/installation protection
Class Code : EC000228
Version : 7
€14,646.30
net
Shipping from:
€55.00
1
Payment methods:
Best offer from:
DETrusted Automa.Net Supplier
Availability:
100 pcs.
In-Stock
Updated at: 20-11-2024
Warranty:
12 months
Estimated Delivery:
05-06 December to United Kingdom
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
A total of 400 Parts In-Stock from 4 Distributors
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (3)

1SDA071804R1 product image
Condition:
New Factory Sealed
Available:
100 pcs.
In-Stock
Updated at: 30-04-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
1
1SDA071804R1 product image
Condition:
New Factory Sealed
Available:
100 pcs.
In-Stock
Updated at: 08-11-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
1SDA071804R1 product image
Condition:
New Factory Sealed
Available:
100 pcs.
In-Stock
Updated at: 08-11-2024
Offer from:
FRTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
€8,202.91

Additional Information

Current Type
AC
Electrical Durability
Ue =< 440 V 7000 cycleUe = 500 ... 690 V 7000 cycle20 cycles per hour
Mechanical Durability
20000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4
Power Loss
425 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
3200 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA(230 V AC) 150 kA(380 V AC) 150 kA(400 V AC) 150 kA(415 V AC) 150 kA(440 V AC) 150 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 100 kAfor 3 s 75 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 150 kA(415 V AC) 150 kA(440 V AC) 150 kA(500 V AC) 100 kA(525 V AC) 100 kA(690 V AC) 100 kA
Rated Uninterrupted Current (Iu)
3200 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Touch LI
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
E4.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
CAD Dimensional Drawing
1SDH001252R0197

Dimensions

Product Net Width
510 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
70 kg

ABB EcoSolutions

ABB EcoSolutions
Yes

Eco Transparency

Environmental Product Declaration - EPD
9AKK108468A1904 9AKK108468A1910

Classifications

ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
EClass
V11.1 : 27370409

Environmental

Environmental Information
9AKK10103A1038 9AKK108467A6707
REACH Declaration
9AKK108466A1425
RoHS Information
9AKK108466A1424
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Circular Value

Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.3 %
Conflict Minerals Reporting Template (CMRT)
9AKK108467A5658
End of Life Instructions
9AKK108468A2363
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA
9AKK108467A8326

Ordering

Order Code US and Canada
ZCVVENBD000A000000XX
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090