- Fuse
- Slow-blow
- Fuse type
- Automatic device
- Rated surge voltage
- 2.5 kV
- Rated voltage
- 250 V AC
- Rated voltage
- 65 V DC
- Rated voltage
- 250 V (AC according to UL 1077)
- Rated voltage
- 72 V (DC according to UL 1077)
- Rated current IN
- 1 A
- Insulation resistance Riso
- > 100 MΩ (500 V DC)
- Rated short-circuit switching capacity Icn
- 6 A (250 V AC / 65 V DC)
- Rated short-circuit switching capacity Icn
- 10 A (30 V DC)
- Short-circuit switching capacity Ik
- 2000 A (250 V AC / UL 1077)
- Short-circuit switching capacity Ik
- 2000 A (72 V DC / UL 1077)
- Dielectric strength
- 3000 V AC (Actuation area)
- Dielectric strength
- 1500 V AC (Installation area)
- Switching cycles, max.
- 6000 (At 1 x In, low-induction)
- Switching cycles, max.
- 3000 (At 1 x In, inductive)
- Switching cycles, max.
- 500 (At 2 x In, inductive)
- Degree of pollution
- 2
- Overvoltage category
- II
- Insulating material group
- IIIb