Schmersal

101190595

1 / 3
thumbnail
thumbnail
thumbnail
Part Number
101190595
ETIM
Group Code : EG000019
Group Description : Relays
Class Description : Device for monitoring of safety-related circuits
Class Code : EC001449
Version : 7
Payment methods:
Best offer from:
USTrusted Automa.Net Supplier
Availability:
6 pcs.
In-Stock
Updated at: 21-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Electrical data - Relay outputs (auxiliary contacts)

Switching capacity, maximum
24 VDC
Switching capacity, maximum
2 A

Electrical data

Frequency range
50 Hz | 60 Hz
Rated operating voltage
48 ... 240 VAC
Rated AC voltage for controls, 50 Hz, minimum
48 VAC
Rated control voltage at AC 50 Hz, maximum
240 VAC
Rated AC voltage for controls, 60 Hz, minimum
48 VAC
Rated control voltage at AC 60 Hz, maximum
240 VAC
Electrical power consumption
2 W
Electrical power consumption
5.1 VA
Contact resistance, maximum
0.1 Ω
Note (Contact resistance)
in new state
Drop-out delay in case of power failure, typically
80 ms
Drop-out delay in case of emergency, typically
20 ms
Pull-in delay at automatic start, maximum, typically
100 ms
Pull-in delay at RESET, typically
20 ms
Material of the contacts, electrical
AgSn0. self-cleaning, positive drive

Note

Note (General)
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.

Mechanical data - Dimensions

Width
45 mm
Height
100 mm
Depth
121 mm

Ambient conditions - Insulation values

Rated impulse withstand voltage U
4 kV
Overvoltage category
III
Degree of pollution
2

Electrical data - Digital Output

Voltage, Utilisation category DC-12
24 VDC
Current, Utilisation category DC-12
0.1 A

General data - Features

Stop-Category
0
Electronic Fuse
Yes
Wire breakage detection
Yes
Cross-circuit detection
Yes
Removable Terminals
Yes
Start input
Yes
Feedback circuit
Yes
Automatic reset function
Yes
Earth connection detection
Yes
Integral system diagnostics, status
Yes
Number of auxiliary contacts
1
Number of LEDs
4
Number of normally closed (NC)
2
Number of safety contacts
3

General data

Standards
EN IEC 62061 | EN ISO 13849-1 | EN IEC 60947-5-1 | EN IEC 60947-5-3 | EN IEC 60947-5-5 | EN IEC 61508 | EN IEC 60204-1 | EN IEC 60947-1
Climatic stress
EN 60068-2-78
Enclosure material
Glass-fibre reinforced thermoplastic, ventilated
Gross weight
300 g

Safety classification

Standards
EN IEC 60947-5-1 | EN IEC 61508
Performance Level, stop 0, up to
e
Category, Stop 0
4
Diagnostic Coverage (DC) Level, Stop 0
≥ 99 %
PFH value, Stop 0
2.00 x 10⁻⁸ /h
Safety Integrity Level (SIL), Stop 0, suitable for applications in
3
Mission time
20 Year(s)
Common Cause Failure (CCF), minimum
65

Wiring example

Note (Wiring diagram)
The wiring diagram is shown with guard doors closed and in de-energised condition. | Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. | The control recognises cross-short, cable break and earth leakages in the monitoring circuit. | 2 channel control shown for a guard-door monitor with two contacts, of which at least one contact has positive break, with external reset button (R). | (H2) = Feedback circuit

Other data

Note (applications)
Guard system | Emergency-Stop button | Pull-wire emergency stop switches | Safety mats

Ambient conditions

Degree of protection of the enclosure
IP40
Degree of protection of the mounting space
IP54
Degree of protection of clips or terminals
IP20
Ambient temperature
-25 ... +60 °C
Storage and transport temperature, minimum
-40 °C
Storage and transport temperature, maximum
+85 °C
Resistance to vibrations
10 ... 55 Hz, Amplitude 0.35 mm
Restistance to shock
30 g / 11 ms

Mechanical data - Connection technique

Termination
rigid or flexible | Screw terminals M20 x 1.5
Terminal designations
IEC/EN 60947-1
Cable section, minimum
0.25 mm²
Cable section, maximum
2.5 mm²
Tightening torque of Clips
0.6 Nm

Electrical data - Safe relay outputs

Voltage, Utilisation category AC-15
230 VAC
Current, Utilisation category AC-15
6 A
Voltage, Utilisation category DC-13
24 VDC
Current, Utilisation category DC-13
6 A
Switching capacity, minimum
10 VDC
Switching capacity, minimum
10 mA
Switching capacity, maximum
250 VAC
Switching capacity, maximum
8 A

Mechanical data

Mechanical life, minimum
10,000,000 Operations
Mounting
Snaps onto standard DIN rail to EN 60715

Specifications

Width
45 mm
Height
100 mm
Depth
121 mm

Approvals - Standards

Certificates
TÜV | cULus | CCC | TILVA

Electrical data - Electromagnetic compatibility (EMC)

EMC rating
EMC-Directive

Electrical data - Digital inputs

Conduction resistance, maximum
40 Ω

Status indication

Indicated operating states
Position relay K2 | Position relay K1