Schneider Electric
ATV12HU40M3
1 / 2
Description
Active Mature
This Altivar 12 variable speed drive can feed 3-phase asynchronous motors in supply line connection. It works at a rated power up to 4kW / 5hp and a rated voltage from 200V to 240V AC. It is designed with heatsink for normal environments and fan-cooled enclosure. Transient overtorque function prevents stoppages by unjamming the machine with extra torque, when needed, this reduces downtime and maintenance costs. It features underload and overload detection, this contribute to protect your installation. The Altivar 12 drive integrates as standard the Modbus communication protocol, which can be accessed via the RJ45 connector located on the underside of the drive. It is designed for simple industry and commercial machines and appliances, such as conveyors, pumps, extractors, access barriers and treadmills. SoMove software compatibility enables saving and transfering of configurations to spare drive, reducing maintenance downtime. It features an optimized application of power and torque for ventilation and pumping applications, this allows up to 30% energy savings.- Country of Origin
- ID
- Part Number
- ATV12HU40M3
- Tariff Code
- 85044095
- EAN
- 3606480071201
- UNSPSC
- 39122001
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 3 pcs.In-StockUpdated at: 21-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Environment
- Product Certifications
- NOM || CSA || C-tick || UL || GOST || RCM || KC
- Maximum Deflection Under Vibratory Load (During Operation)
- 1.5 mm at 2...13 Hz
- Standards
- UL 508C || UL 618000-5-1 || IEC 61800-5-1 || IEC 61800-3
- Vibration Resistance
- 1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm peak to peak 3-13 Hz) - drive unmounted on symmetrical DIN rail - IEC 60068-2-6
- Shock Resistance
- 15 gn 11 ms IEC 60068-2-27
- Regulation Loop
- adjustable PID regulator
- Operating Altitude
- <= 3280.84 ft (1000 m) without derating || > 3280.84...9842.52 ft (> 1000...3000 m) with current derating 1 % per 100 m
- Overvoltage Category
- class III
- Environmental Class (During Operation)
- class 3C3 according to IEC 60721-3-3 || class 3S2 according to IEC 60721-3-3
- Electromagnetic Emission
- radiated emissions environment 1 category C2 IEC 61800-3 2...16 kHz shielded motor cable || conducted emissions IEC 61800-3
- Maximum Acceleration Under Shock Impact (During Operation)
- 150 m/s² at 11 ms
- Pollution Degree
- 2
- Electromagnetic Compatibility
- electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || electrostatic discharge immunity test level 3 IEC 61000-4-2 || immunity to conducted disturbances level 3 IEC 61000-4-6 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || surge immunity test level 3 IEC 61000-4-5 || voltage dips and interruptions immunity test IEC 61000-4-11
- Ambient Air Temperature For Operation
- -10-50 °C without derating || 50-60 °C with current derating 2.2 % per °C
- Volume Of Cooling Air
- 16.4 m3/h
- Marking
- CE
- Maximum Acceleration Under Vibrational Stress (During Operation)
- 10 m/s² at 13...200 Hz
- Noise Level
- 50 dB
- Ambient Air Temperature For Storage
- -25-70 °C
- Relative Humidity
- 5-95 % without condensation IEC 60068-2-3 || 5-95 % without dripping water IEC 60068-2-3
- Assembly Style
- with heat sink
- Operating Position
- vertical +/- 10 degree
- Ambient Air Transport Temperature
- -25-70 °C
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Rohs Exemption Information
- Yes
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Prospective Line Isc
- 5 kA
- Network Frequency
- 50-60 Hz
- Power Dissipation In W
- forced cooling 128.0 W
- Line Current
- 23.8 A 100 V heavy duty) || 19.9 A 120 V heavy duty)
- Asynchronous Motor Control Profile
- quadratic voltage/frequency ratio || voltage/frequency ratio (V/f) || sensorless flux vector control
- Relative Symmetric Network Frequency Tolerance
- 5 %
- Apparent Power
- 8.3 kVA 240 V heavy duty)
- Net Weight
- 2 kg
- Type Of Polarization
- no impedance
- Frequency Resolution
- analog input converter A/D, 10 bits || display unit 0.1 Hz
- Switching Frequency
- 2...16 kHz adjustable || 4...16 kHz with derating factor
- Maximum Transient Current
- 25.0 A 60 s heavy duty) || 27.6 A 2 s heavy duty)
- Communication Service
- read holding registers (03) 29 words || write single register (06) 29 words || write multiple registers (16) 27 words || read/write multiple registers (23) 4/4 words || read device identification (43)
- Analogue Input Number
- 1
- Motor Slip Compensation
- preset in factory || adjustable
- Discrete Output Number
- 2
- Method Of Access
- server Modbus serial
- Number Of Addresses
- 1-247
- Speed Range
- 1-20
- Discrete Input Number
- 4
- Linearity Error
- +/- 0.3 % of maximum value analogue input
- Width
- 140 mm
- Transmission Rate
- 9.6 kbit/s || 19.2 kbit/s || 38.4 kbit/s
- Depth
- 141.2 mm
- Sampling Duration
- 20 ms +/- 1 ms logic input || 10 ms analogue input
- Maximum Output Frequency
- 4 kHz
- Height
- 184 mm
- Acceleration And Deceleration Ramps
- S || U || linear from 0 to 999.9 s
- Time Constant
- 20 ms +/- 1 ms for reference change
- Maximum Output Voltage
- 240 V
- Base Load Current At High Overload
- 16.7 A
- Speed Drive Output Frequency
- 0.5-400 Hz
- Transmission Frame
- RTU
- Relay Output Number
- 1
- Transient Overtorque
- 150-170 % of nominal motor torque depending on drive rating and type of motor
- Data Format
- 8 bits, configurable odd, even or no parity
- Connector Type
- 1 RJ45
- Analogue Output Number
- 1
- Physical Interface
- 2-wire RS 485
- Insulation
- electrical between power and control
- Tightening Torque
- 1.2 N.m
- Continuous Output Current
- 16.7 A 4 kHz
- Nominal Switching Frequency
- 4 kHz
- Quantity Per Set
- set of 1
- Braking To Standstill
- by DC injection
- Protection Type
- line supply overvoltage || line supply undervoltage || overcurrent between output phases and earth || overheating protection || short-circuit between motor phases || against input phase loss in three-phase || thermal motor protection via the drive by continuous calculation of I²t
Specifications
- Product Or Component Type
- variable speed drive
- Ip Degree Of Protection
- IP20
- Communication Port Protocol
- Modbus
- Nominal Output Current
- 16.7 A
- Product Specific Application
- simple machine
- Maximum Horse Power Rating
- 5 hp
- Supply Frequency
- 50/60 Hz +/- 5 %
- Range Of Product
- Altivar 12
- Motor Power Kw
- 4 kW
- [Us] Rated Supply Voltage
- 200...240 V - 15...10 %
- Mounting Mode
- cabinet mount
- Emc Filter
- without EMC filter