1 / 1
thumbnail

Description

Active Mature
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Country of Origin
CZ
Part Number
LC1D65F7
Tariff Code
85364900
EAN
3389110436877
UNSPSC
39121529
Payment methods:
Best offer from:
DETrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 21-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
A total of 23 Parts In-Stock from 7 Distributors
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (6)

Best offer
LC1D65F7 product image
Schneider Electric

LC1D65F7

Condition:
New Factory Sealed
Available:
1 pc.
In-Stock
Updated at: 30-04-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
1
LC1D65F7 product image
Schneider Electric

LC1D65F7

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 22-11-2024
Offer from:
FRTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
24 months
1
LC1D65F7 product image
Schneider Electric

LC1D65F7

Condition:
New Surplus
Available:
8 pcs.
In-Stock
Updated at: 22-11-2024
Offer from:
COTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC1D65F7 product image
Schneider Electric

LC1D65F7

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 08-11-2024
Offer from:
FRTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC1D65F7 product image
Schneider Electric

LC1D65F7

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 08-11-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC1D65F7 product image
Schneider Electric

LC1D65F7

Condition:
New Surplus
Available:
10 pcs.
In-Stock
Updated at: 22-11-2024
Offer from:
HKAutoma.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Environment

Product Certifications
CCC || GOST || CSA || RINA || LROS (Lloyds register of shipping) || BV || GL || UL || UKCA || DNV
Height
127 mm
Standards
EN 60947-5-1 || UL 508 || CSA C22.2 No 14 || IEC 60947-5-1 || EN 60947-4-1
Climatic Withstand
IACS E10 exposure to damp heat
Net Weight
2.185 kg
Flame Retardance
V1 conforming to UL 94
Ip Degree Of Protection
IP2X VDE 0106 || IP2X IEC 60529
Mechanical Robustness
shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor opened 10 Gn for 11 ms)
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
85 mm
Depth
176 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110205EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on energisation between NC and NO contacts || 1.5 ms on de-energisation between NC and NO contacts
Minimum Switching Current
5 mA for control circuit
Power Dissipation Per Pole
6.4 W AC-1 || 4.2 W AC-3e || 4.2 W AC-3
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
80 A (at 60 °C) for power circuit || 10 A (at 60 °C) for control circuit
Control Circuit Voltage Limits
0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz || 0.75...1.25 Uc -40-60 °C operational DC || 0.1...0.3 Uc -40-70 °C drop-out DC
Mounting Support
rail || plate
Control Circuit Type
DC standard
Safety Reliability Level
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 || B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
Hold-In Power Consumption In W
7.4-7.4 W 20 °C
Insulation Resistance
> 10 MOhm for control circuit
Rated Breaking Capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
140 A AC for control circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947 || 250 A DC for control circuit conforming to IEC 60947-5-1
Associated Fuse Rating
125 A gG at <= 690 V coordination type 2 for power circuit || 160 A gG at <= 690 V coordination type 1 for power circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 10 A gG for control circuit conforming to IEC 60947-5-1
Inrush Power In Va
160-160 VA cos phi 0.75 (at 20 °C)
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947
Pole Contact Composition
3 NO
Connections - Terminals
control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: rigid || power circuit: screw terminals 2 2.5-16 mm² - cable stiffness: rigid without cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw terminals 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: flexible with cable end || power circuit: screw terminals 2 2.5-10 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid
Coil Technology
built-in bidirectional peak limiting diode suppressor
Time Constant
34 ms
Operating Time
12...26 ms closing || 50 ms closing || 20 ms opening
Minimum Switching Voltage
17 V for control circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw terminal flat Ø 6 to Ø 8 mm || control circuit 1.7 N.m screw clamp terminal pozidriv No 2 || control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm
Mechanical Durability
10000000 cycles
Inrush Power In W
19-19 W 20 °C)
Auxiliary Contacts Type
mirror contact 1 NC IEC 60947-4-1 || mechanically linked 1 NO + 1 NC IEC 60947-5-1
Compatibility Code
LC1D
Hold-In Power Consumption In Va
15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
Overvoltage Category
III
Maximum Horse Power Rating
10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp at 575/600 V AC 60 Hz for 3 phase motors || 5 hp at 115 V AC 60 Hz for 1 phase motors
Motor Power Kw
11 kW at 400 V AC 50 Hz (AC-4) || 30 kW at 380...400 V AC 50 Hz (AC-3) || 37 kW at 500 V AC 50 Hz (AC-3) || 37 kW at 660...690 V AC 50 Hz (AC-3) || 18.5 kW at 220...230 V AC 50 Hz (AC-3) || 30 kW at 415 V AC 50 Hz (AC-3) || 37 kW at 1000 V AC 50 Hz (AC-3) || 30 kW at 440 V AC 50 Hz (AC-3e) || 30 kW at 380...400 V AC 50 Hz (AC-3e) || 37 kW at 500 V AC 50 Hz (AC-3e) || 37 kW at 660...690 V AC 50 Hz (AC-3e) || 18.5 kW at 220...230 V AC 50 Hz (AC-3e) || 30 kW at 415 V AC 50 Hz (AC-3e) || 37 kW at 1000 V AC 50 Hz (AC-3e) || 30 kW at 380...400 V AC 50 Hz || 30 kW at 440 V AC 50 Hz
[Ui] Rated Insulation Voltage
control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL IEC 60947-1 || control circuit 690 V IEC 60947-1 || power circuit 690 V CSA IEC 60947-1 || control circuit 600 V CSA
Protective Cover
with

Specifications

[Uc] Control Circuit Voltage
110 V DC
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz
Range Of Product
TeSys Deca
Contactor Application
resistive load || motor control
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-2 || AC-4 || AC-1 || AC-3e
[Ie] Rated Operational Current
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit || 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Poles Description
3P
Device Short Name
LC1D