- Product Certifications
- BV || CCC || UL || CB || RINA || ABS || RMRoS || LROS (Lloyds register of shipping) || DNV || UKCA
- Power Dissipation Per Pole
- 44 W AC-1 || 31 W AC-3
- Average Impedance
- 0.28 mOhm - Ith 400 A 50 Hz
- [Ith] Conventional Free Air Thermal Current
- 400 A 40 °C
- Control Circuit Voltage Limits
- operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.35...0.55 Uc 40...400 Hz 55 °C)
- Standards
- EN 60947-4-1 || IEC 60947-4-1 || IEC 60947-1 || JIS C8201-4-1 || EN 60947-1
- Mounting Support
- plate
- Control Circuit Type
- AC 40...400 Hz
- Rated Breaking Capacity
- 2640 A IEC 60947-4-1
- Associated Fuse Rating
- 400 A aM <= 440 V || 500 A gG <= 440 V
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Inrush Power In Va
- 650-650 VA, 40...400 Hz 0.9 20 °C)
- Connections - Terminals
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit lugs-ring terminals 1 240-240 mm² || power circuit bar 2 30 x 5 mm || power circuit bolted connection
- Pole Contact Composition
- 3 NO
- Operating Time
- 40...65 ms closing || 100...170 ms opening
- Maximum Operating Rate
- 2400 cyc/h 55 °C
- Mechanical Durability
- 10 Mcycles
- Tightening Torque
- control circuit 1.2 N.m || power circuit 35 N.m
- Compatibility Code
- LC1F
- Hold-In Power Consumption In Va
- 10-10 VA, 40...400 Hz 0.9 20 °C)
- Overvoltage Category
- III
- Motor Power Kw
- 160 kW 380...400 V AC 50/60 Hz AC-3) || 180 kW 415 V AC 50/60 Hz AC-3) || 200 kW 440 V AC 50/60 Hz AC-3) || 200 kW 500 V AC 50/60 Hz AC-3) || 220 kW 660...690 V AC 50/60 Hz AC-3) || 160 kW 1000 V AC 50/60 Hz AC-3) || 100 kW 220...230 V AC 50/60 Hz AC-3) || 59 kW 400 V AC 50/60 Hz AC-4)
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
- [Icw] Rated Short-Time Withstand Current
- 2650 A 40 °C - 10 s || 1800 A 40 °C - 30 s || 1300 A 40 °C - 1 min || 900 A 40 °C - 3 min || 750 A 40 °C - 10 min
- Heat Dissipation
- 8-8 W