Schneider Electric
M9U21240
1 / 3
Description
Active Mature
This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 2P circuit breaker with 2 protected poles, 40A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 20kA at 220VDC conforming to EN/IEC 60947-2 standard and 20kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.- Country of Origin
- CN
- Part Number
- M9U21240
- Tariff Code
- 85362010
- EAN
- 3606480741845
- UNSPSC
- 39121603
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 5 pcs.In-StockUpdated at: 21-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Specifications
- Line Rated Current
- 40 A 25 °C EN/IEC 60947-2
- Curve Code
- C
- Number Of Protected Poles
- 2
- Network Type
- DC
- Standards
- EN/IEC 60947-2 || GB 14048.2 || UL 1077
- Product Certifications
- IEC || CCC || UR
- Product Or Component Type
- miniature circuit-breaker
- Product Name
- Multi9 C60H-DC
- Utilisation Category
- category A EN/IEC 60947-2
- Range
- Multi9
- Breaking Capacity
- 20 kA Icu 220 V DC EN/IEC 60947-2 || 10 kA Icu 440 V DC EN/IEC 60947-2 || 6 kA Icu 500 V DC EN/IEC 60947-2 || 5 kA AIR 12...500 V DC UL 1077 || 20 kA Icu 220 V DC GB 14048.2 || 10 kA Icu 440 V DC GB 14048.2 || 6 kA Icu 500 V DC GB 14048.2
- Suitability For Isolation
- yes EN/IEC 60947-2
- Poles Description
- 2P
- Device Application
- distribution
- Device Short Name
- C60H-DC
- Trip Unit Technology
- thermal-magnetic
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2308050EN
- Sustainable Offer Status
- Green Premium product
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- Reach Free Of Svhc
- Yes
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- [Ics] Rated Service Breaking Capacity
- 7.5 kA 75 % EN/IEC 60947-2 - 440 V DC || 4.5 kA 75 % EN/IEC 60947-2 - 500 V DC || 15 kA 75 % EN/IEC 60947-2 - 220 V DC || 7.5 kA 75 % GB 14048.2 - 440 V DC || 4.5 kA 75 % GB 14048.2 - 500 V DC || 15 kA 75 % GB 14048.2 - 220 V DC
- Height
- 81 mm
- Contact Position Indicator
- yes
- Earth-Leakage Protection
- without
- Mounting Support
- DIN rail
- 9 Mm Pitches
- 4
- Net Weight
- 0.128 kg
- Wire Stripping Length
- 14 mm for top or bottom connection
- Control Type
- toggle
- Connections - Terminals
- tunnel type terminal top or bottom) 1-35 mm² AWG 18...AWG 2) - rigid stranded || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - flexible || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - flexible with ferrule || tunnel type terminal top or bottom) - 2 1-16 mm² AWG 18...AWG 6) - rigid stranded || tunnel type terminal top or bottom) - 2 1-16 mm² AWG 18...AWG 6) - flexible || tunnel type terminal top or bottom) - 2 1-16 mm² AWG 18...AWG 6) - flexible with ferrule || tunnel type terminal top or bottom) - 3 4-4 mm² AWG 6) - flexible stranded
- [Ui] Rated Insulation Voltage
- 500 V DC EN/IEC 60947-2
- Mounting Mode
- clip-on
- Electrical Durability
- 3000 cycles 250 V DC L/R = 2 ms || 6000 cycles 250 V DC
- Mechanical Durability
- 20000 cycles
- Local Signalling
- ON/OFF indication
- [Uimp] Rated Impulse Withstand Voltage
- 6 kVEN/IEC 60947-2
- Color
- Gray
- Width
- 36 mm
- Provision For Padlocking
- padlockable
- Depth
- 73 mm
- Tightening Torque
- 3.5-3.5 N.m top or bottom
- Magnetic Tripping Limit
- 7...10 x In DC
- [Ue] Rated Operational Voltage
- 220 V DC || 440 V DC || 500 V DC
Environment
- Ambient Air Temperature For Operation
- -25-70 °C
- Tropicalisation
- 2 IEC 60068-2 || 2 GB 14048.2
- Ip Degree Of Protection
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Pollution Degree
- 3 EN/IEC 60947-2
- Ambient Air Temperature For Storage
- -40-85 °C
- Relative Humidity
- 95-95 % 55-55 °C
- Heat Dissipation
- 8.6-8.6 W 440 V - 40 A