- Maximum Switching Capacity
- 3000 VA/336 W
- Safety Reliability Data
- B10d = 100000
- Continuous Output Current
- 10 A
- Operating Rate
- <= 1200 cycles/hour under load || <= 18000 cycles/hour no-load
- Protection Category
- RT I
- Test Levels
- level A group mounting
- Contacts Material
- AgNi
- Reset Time
- 20 ms
- Shape Of Pin
- flat
- Net Weight
- 0.037 kg
- Cad Overall Height
- 79 mm
- Maximum Switching Voltage
- 250 V IEC
- Average Resistance
- 160 Ohm 20 °C +/- 10 %
- Device Presentation
- complete product
- Average Coil Consumption
- 0.9 W
- Rated Operational Voltage Limits
- 9.6...13.2 V DC
- [Ie] Rated Operational Current
- 12 A 28 V DC) NO IEC || 12 A 250 V AC) NO IEC || 6 A 28 V DC) NC IEC || 6 A 250 V AC) NC IEC || 12 A 28 V DC) UL || 12 A 277 V AC) UL
- [Ui] Rated Insulation Voltage
- 250 V IEC || 300 V CSA || 300 V UL
- Electrical Durability
- 100000 cycles resistive
- Mechanical Durability
- 10000000 cycles
- Operating Position
- any position
- Operating Time
- 20 ms
- Load Current
- 12 A 250 V AC || 12 A 28 V DC
- Drop-Out Voltage Threshold
- >= 0.1 Uc
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV 1.2/50 µs
- Minimum Switching Capacity
- 170 mW 10 mA, 17 V
- Cad Overall Depth
- 78.45 mm