Schneider Electric
TPRSS038
1 / 1
Description
Active Mature
TeSys island direct SIL starter, 3 poles, 38A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 38A and motors up to 18,5kW@400V / 20hp@480V. In association with a TPRSM001 module and an external safety device, it can be used for safety related systems conforming to IEC 61508. It provides motor protection functions including thermal overload (setting 0.76-38A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).- Country of Origin
- FR
- Part Number
- TPRSS038
- Tariff Code
- 85365080
- EAN
- 3606489832810
- UNSPSC
- 39121521
£148.50
net£165.00
Shipping from:
£35.00
1
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 2 pcs.In-StockUpdated at: 21-11-2024
- Warranty:
- 6 months
- Estimated Delivery:
- 25-26 November to United Kingdom
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Environment
- Ambient Air Temperature For Operation
- -10-50 °C without derating || 50-60 °C with current derating
- Shock Resistance
- 15 gn 11 ms) IEC 60068-2-27
- Vibration Resistance
- 1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
- Electromagnetic Compatibility
- electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4 || surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5 || surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5 || conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
- Pollution Degree
- 2
- Ambient Air Temperature For Storage
- -25-70 °C
- Protective Treatment
- TC
- Relative Humidity
- 5-95 %
- Ip Degree Of Protection
- IP20
- Operating Altitude
- 0...6561.68 ft (0...2000 m) without derating
- Fire Resistance
- 960 °C UL 94 || 850 °C IEC 60695-2-1 || 650 °C IEC 60695-2-12
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1904009EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI1904009EN
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free plastic parts product
Complementary
- Mounting Mode
- horizontal and vertical 35 mm symmetrical DIN rail)
- Height
- 121 mm
- Product Certifications
- CSA || EAC || UL || CCC
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Standards
- EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
- Connections - Terminals
- screw-clamp terminals 1 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 2 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 1 2.5-10 mm² AWG 14...AWG 8)flexible without cable end || screw-clamp terminals 2 2.5-10 mm² AWG 14...AWG 8)flexible without cable end || screw-clamp terminals 1 1.5-10 mm² AWG 16...AWG 10)flexible with cable end || screw-clamp terminals 2 1.5-6 mm² AWG 16...AWG 10)flexible with cable end
- Net Weight
- 0.718 kg
- Metering Type
- time device ON || time device switch ON || number of faults || number of switching cycles || number of device power cycles || average current Iavg || average voltage Vavg || max current Imax || max voltage Vmax || active and reactive power with voltage module || active and reactive energy with voltage module || true power factor with voltage module
- Maximum Operating Rate
- 3600 cyc/mn AC-3
- Local Signalling
- for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
- Electrical Durability
- 1.4 Mcycles 38 A AC-3 440 V || 2 Mcycles 40 A AC-1 440 V
- Mechanical Durability
- 30 Mcycles
- Safety Function
- safe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module || safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module
- Operating Time
- < 100 ms closing || < 30 ms opening
- Width
- 45 mm
- Depth
- 115 mm
- Tightening Torque
- 2.5-2.5 N.m flat Ø 6 mm || 2.5-2.5 N.m Philips No 3
- Protection Type
- thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || rapid restart lockout || phase sequence || phase reversal || phase loss || phase unbalance || ground current
- Safety Level
- SIL 2 conforming to IEC 61508 in single channel system architecture || SILCL 2 conforming to IEC 62061 in single channel system architecture || PL = d category 2 conforming to ISO 13849-1 in single channel system architecture
Specifications
- Current Consumption
- 160 mA contactor sealed || 160 mA contactor closing
- Power Dissipation In W
- 11.8 W at Ie AC-3
- Power Dissipation Per Pole
- 2.9 W AC-3 - Ith 38 A || 3.2 W AC-1 - Ith 40 A
- Average Impedance
- 2 mOhm - Ith 40 A 50 Hz
- Reset
- remotely or automatically
- [Ith] Conventional Free Air Thermal Current
- 40 A (at 50 °C)
- [Uc] Control Circuit Voltage
- 24 V DC supplied by the bus coupler
- Rated Breaking Capacity
- 550 A at 440 V conforming to IEC 60947
- Product Or Component Type
- SIL motor starter
- Irms Rated Making Capacity
- 550 A at 440 V conforming to IEC 60947
- Product Name
- TeSys island
- Thermal Overload Class
- class 5…30
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-1
- Range
- TeSys
- Device Presentation
- direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
- Motor Starter Type
- direct on line
- Utilisation Category
- AC-1 || AC-2 || AC-3 || AC-4
- Function Available
- upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module || safe stop function available when connected with a TPRSM module
- [Ie] Rated Operational Current
- 38 A (at <50 °C) at <= 440 V AC-3 || 40 A (at <50 °C) at <= 440 V AC-1
- Overvoltage Category
- III for Ue <= 480 V || II for Ue <= 690 V
- Thermal Protection Adjustment Range
- 0.76-38 A
- Product Compatibility
- TPRBC bus coupler || TPRVM voltage interface module || TPRSM SIL interface module
- [Ue] Rated Operational Voltage
- <= 480 V AC 47...63 Hz for overvoltage cat. III || <= 690 V AC 47...63 Hz for overvoltage cat. II
- Maximum Horse Power Rating
- 2 hp at 120 V AC 60 Hz for 1 phase motors || 5 hp at 240 V AC 60 Hz for 1 phase motors || 10 hp at 208 V AC 60 Hz for 3 phase motors || 10 hp at 240 V AC 60 Hz for 3 phase motors || 20 hp at 480 V AC 60 Hz for 3 phase motors || 25 hp at 600 V AC 60 Hz for 3 phase motors
- Motor Power Kw
- 9 kW at 230 V 50 Hz (AC-3) || 18.5 kW at 380...415 V 50 Hz (AC-3) || 18.5 kW at 440 V 50 Hz (AC-3) || 18.5 kW at 500 V 50 Hz (AC-3) || 18.5 kW at 690 V 50 Hz (AC-3)
- [Ui] Rated Insulation Voltage
- 690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
- Device Short Name
- TPRSS
- Poles Description
- 3P 3 NO
- [Icw] Rated Short-Time Withstand Current
- 430 A 40 °C - 1 s || 310 A 40 °C - 10 s || 150 A 40 °C - 1 min || 60 A 40 °C - 10 min
CAD Models
traceparts
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther