- Height
- 151.5 mm
- [Ith] Conventional Free Air Thermal Current
- 16 A relay output || 6.5 A static output circuit
- Mounting Support
- mounting plate
- Output Thermal Current
- 4 A for both outputs simultaneously || 6 A for 1 output and 2 A for the other relay output
- Power Consumption In W
- 12 W
- Minimum Output Voltage
- 17 V relay output
- Response Time
- configurable : 20 ms or 30 ms with software XPSMCWIN
- Data Format
- 1 start bit/8 data bits || 1 stop bit even or odd || 2 stop bits without parity || RTU (Remote Terminal Unit) mode
- Minimum Output Current
- 10 mA relay output
- Associated Fuse Rating
- 16 A gL power supply || 4 A gL relay output || 6 A fast blow relay output
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV III IEC 60647-5-1, DIN VDE 0110 part 1
- Net Weight
- 0.82 kg
- Output Type
- 2 relays, 2 NO contacts (4 NO total) || solid state, 6, volt-free
- [Ui] Rated Insulation Voltage
- 300 V 2)IEC 60647-5-1, DIN VDE 0110 part 1
- Parity
- even Modbus || no Modbus || odd Modbus
- Exchange Size
- 14 words
- Supported Modbus Function
- 01 8-bit output data/32-bit input data || 02 32-bit input data/8-bit output data || 03 information and errors
- Method Of Access
- slave
- Local Signalling
- 30 LEDs
- Number Of Addresses
- 1-247 Modbus
- Maximum Line Resistance
- 100 Ohm <2000 m
- Input Protection Type
- external fuse 16 A
- Width
- 74 mm
- Depth
- 153 mm
- [Uc] Control Circuit Voltage
- 28.8 V
- Function Of Module
- dynamic monitoring of hydraulic valves on linear presses || eccentric press || emergency stop monitoring, with or without time delay, 1 or 2-channel wiring || enabling switch monitoring, 2 or 3 contacts || foot switch monitoring || guard monitoring for injection presses and blowing machines || guard monitoring with 1 or 2 limit switches || hydraulic press || magnetic switch monitoring category 4 EN/IEC 61496 || monitoring safety stop at top dead centre on eccentric press category 3 EN 574/ISO 13851 || muting function of light curtains || position selector || safety mat monitoring || safety time delays || shaft/chain breaking monitor || zero speed detection || light curtain monitoring category 4 IEC 61496 || two-hand control category 3 EN 574/ISO 13851
- Synchronisation Time Between Inputs
- depending on configuration selected
- Breaking Capacity
- 2 A 24 V static output circuit || 1.5 A 24 V DC-13)50 ms relay output
- Breaking Capacity
- 180 VA holding AC-15 C300 relay output || 1800 VA inrush AC-15 C300 relay output