Wago

787-1226

1 / 3
thumbnail
thumbnail
thumbnail
Part Number
787-1226
Tariff Code
85044082900
UPC
4055143415040
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : DC-power supply
Class Code : EC002540
Version : 7
Payment methods:
Best offer from:
ITTrusted Automa.Net Supplier
Availability:
4 pcs.
In-Stock
Updated at: 22-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Safety And Protection

Isolation voltage (pri.-sec.)
DC 4.242 kV
Protection class
I
Protection type
IP20; per EN 60529
Resistance to reverse feed
≤ DC 35 V
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
≤ 31 VDC (in the event of a fault)
Short-circuit-protected
Yes
Open-circuit-proof
Yes
Parallel operation
Yes
Series operation
Yes
MTBF
> 500,000 h (per IEC 61709)

Environmental Requirements

Ambient temperature (operation)
-25 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Relative humidity
≤ 95% (no condensation permissible)
Derating
-2.66 %/K (> 55 °C)

Connection Data

Connection type 1
Input/output
Connection technology
Push-in CAGE CLAMP®
WAGO connector
picoMAX® 5.0, WAGO 2092 Series
Solid conductor
0.2 … 2.5 mm² / 24 … 12 AWG
Fine-stranded conductor
0.2 … 2.5 mm² / 24 … 12 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Signaling And Communication

Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (Uo)

Physical Data

Width
144 mm / 5.669 inches
Height
90 mm / 3.543 inches
Depth
56 mm / 2.205 inches
Depth from upper-edge of DIN-rail
52.5 mm / 2.067 inches
Note (dimensions)
Depth: 48 mm (without cover)

Material Data

Flammability class per UL94
V0
Fire load
0.243 MJ
Weight
510.000 g

Input

Phases
1
Nominal input voltage Ui nom
1 x AC 100 … 120 V; AC 200 … 240 V
Input voltage range
1 x AC 90 … 132 V; AC 180 … 264 V; DC 250 … 375 V
Input voltage derating
-2 %/V (< 100 VAC)
Nominal mains frequency range
47 … 63 Hz; 0 Hz
Input current Ii
≤ 3.8 A
Discharge current
≤ 0.25 mA
Inrush current
≤ 20 A
Power factor
≥ 0.5
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 30 ms

Output

Nominal output voltage Uo nom
DC 24 V (SELV)
Output voltage range
DC 22 … 27 V (adjustable)
Default setting
DC 24 V
Nominal output current Io nom
6 A; 4.8 A (< 110 VAC)
Nominal output power
150 W
Deviation
≤ 1 %
Deviation, dynamic load change 10 … 90 %
≤ 1 %
Residual ripple
≤ 100 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.05 … 1.35 x Io nom); Shutdown and automatic restart in the event of a short circuit or permanent overload

Standards And Specifications

Conformity marking
CE
Standards/specifications
EN 61204-3 || EN 60335-1 || EN 62368-1 || UL 60950-1 || UL 508

Mechanical Data

Mounting type
DIN-35 rail || Screw mount (back)

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
CN
GTIN
4055143415040
Customs tariff number
85044083900

Efficiency/Power Losses

Power loss Pl
≤ 0.4 W
Power loss (max.) Pl (max.)
16.5 W (100 VAC / 24 VDC; 6 A)
Efficiency (typ.)
90 % (230 VAC); 89 % (110 VAC)

<B>Circuit Protection</B>

Internal fuse
T 3.15 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A (C characteristic), 10 A (B characteristic) or higher