Wago

788-720

1 / 1
thumbnail
Part Number
788-720
Tariff Code
85365005000
UPC
4045454743888
ETIM
Group Code : EG000019
Group Description : Relays
Class Description : Optocoupler
Class Code : EC001504
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Safety And Protection

Pollution degree
2
Dielectric strength (control/load circuit) (AC, 1 min)
3.75 kVrms
Protection type
IP20

Load Circuit

Circuit type
2-wire connection || Zero-voltage switching
Limiting continuous current
1 A
Nominal output voltage
AC 230 V
Output voltage range
AC 24 … 240 V
Voltage drop
≤ 1.1 VAC
Turn-on time
≤ 10 ms
Turn-off time
≤ 10 ms
Switching frequency
50 Hz / 60 Hz

Environmental Requirements

Ambient temperature (operation at UN)
-20 … +60 °C
Ambient temperature UL (operation at UN)
-40 … +60 °C
Ambient temperature (storage)
-40 … +70 °C
Processing temperature
-25 … +50 °C
Temperature range of connection cable
≥ (Tambient + 20 K)

Connection Data

Connection technology
Push-in CAGE CLAMP®
Solid conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor
0.34 … 2.5 mm² / 22 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Control Circuit

Nominal input voltage UN
DC 24 V
Input voltage range (low level)
DC 0 … 4 V
Input voltage range (high level)
DC 18 … 30 V
Nominal input current at UN
7 mA

Physical Data

Width
15 mm / 0.591 inches
Height from upper-edge of DIN-rail
54 mm / 2.126 inches
Depth
86 mm / 3.386 inches

Material Data

Color
Gray
Fire load
0.693 MJ
Weight
41.252 g

Standards And Specifications

Standards/specifications
EN 61000-6-2 || EN 61000-6-3 || EN 61373 || EN 61010-2-201 || UL 508 (max. 40 °C/2.5 A)

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4045454743888
Customs tariff number
85365005000

Notes

Note
A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.

Signaling

Status indicator
Red LED