- Height
- 125 mm
- Temperature Drift
- 10 %oFS/°C +/- 10 V 60 °C || 30 %oFS/°C 0...20 mA 60 °C
- Isolation Between Channels And Ground
- 500 V AC for 1 minute
- Current Consumption
- 150 mA 24 V DC actuator || 530 mA 24 V DC base
- Data Format
- full 16 bits signed
- Marking
- CE
- Fail State
- reset to full scale || hold || reset to zero
- External Power Requirement
- +/- 30 V DC || 24 V DC
- Net Weight
- 0.215 kg
- Analogue Output Range
- +/- 10 V 12 bits + sign >= 1 kOhm || 0...20 mA 12 bits + sign <= 0.6 kOhm
- Absolute Accuracy Error
- +/- 0.2 % of full scale +/- 10 V 25 °C || +/- 0.25 % full scale +/- 10 V 60 °C || +/- 0.3 % of full scale 0...20 mA 25 °C || +/- 0.4 % of full scale 0...20 mA 60 °C
- Full Scale
- 10 V +/- 10 V || 2 mA 0...20 mA
- Maximum Power Dissipation In W
- 8.5 W
- Analogue Output Number
- 4
- Output Short-Circuit Protection
- with in voltage circuit
- Permissible Common Mode Voltage
- 250 V 47...63 Hz AC between channels to ground || 250 V 47...63 Hz DC
- Local Signalling
- for channel status 4 LEDs
- Module Format
- standard
- Update Time
- 2 ms
- Width
- 141.5 mm
- Depth
- 47.5 mm
- Protection Type
- internal 2 A slow-blow
- Reverse Polarity Protection
- internal
- Maximum Load Capacitance
- 1 µF