Schneider Electric
ATS48C11Y
1 / 2
Description
Active Mature
This Altistart 48 soft start/soft stop unit is a controller with 6 thyristors used for torque-controlled soft starting and stopping of three-phase asynchronous motors. It offers soft starting and deceleration functions along with machine and motor protection functions, as well as functions for communicating with control systems. It works at a rated supply voltage from 208V to 690V AC and up to 110A rating. Altistart 48 torque control enables starting without mechanical stress and smooth control of hydraulic transitions, with a single acceleration ramp making adjustments is quick and easy, whatever the load. It is suitable for motors with power rating up to 100hp (at 575V) / 90kW (at 690V) for standards applications and 75hp (at 575V) / 75kW (at 690V) for severe applications. It weighs 8.3kg and its dimensions are, 190mm wide, 290mm high, 235mm deep. It is designed for use in the most common applications for centrifugal machines, pumps, fans, compressors and conveyors, which are primarily to be found in the construction, food and beverage and chemical industries. It complies with IEC/EN 60947-4-2 standard and is certified CE, UL, CSA, DNV, C-Tick, GOST, CCC, NOM, SEPRO, and TCF. The Altistart 48 is connected directly to the Modbus bus via its RJ45 connector port, It can also be connected to Ethernet, Fipio, Profibus DP and DeviceNet networks via a module (bridge or gateway) to order separately. It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. Altistart 48 delivers high performance with its Torque Control System (TCS) for controlled starting and deceleration, an easy integration in enclosures and control systems. This range provides also continual improvement of your machine operation by reducing mechanical or hydraulic stress and limiting energy loss and temperature rise, plus more.- Country of Origin
- ID
- Part Number
- ATS48C11Y
- Tariff Code
- 85371098
- EAN
- 3389110982343
- UNSPSC
- 39121521
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 4 pcs.In-StockUpdated at: 21-11-2024
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Specifications
- Product Destination
- asynchronous motors
- Range Of Product
- Altistart 48
- Product Or Component Type
- soft starter
- Motor Power Kw
- 22 kW 230 V for severe applications || 30 kW 230 V for standard applications || 45 kW 400 V for severe applications || 45 kW 440 V for severe applications || 55 kW 400 V for standard applications || 55 kW 440 V for standard applications || 55 kW 500 V for severe applications || 55 kW 525 V for severe applications || 75 kW 500 V for standard applications || 75 kW 525 V for standard applications || 75 kW 660 V for severe applications || 75 kW 690 V for severe applications || 90 kW 660 V for standard applications || 90 kW 690 V for standard applications
- Utilisation Category
- AC-53A
- [Us] Rated Supply Voltage
- 208...690 V - 15...10 %
- Product Specific Application
- heavy duty industry and pumps
- Maximum Horse Power Rating
- 100 hp 575 V for standard applications || 25 hp 208 V for severe applications || 30 hp 208 V for standard applications || 30 hp 230 V for severe applications || 40 hp 230 V for standard applications || 60 hp 460 V for severe applications || 75 hp 460 V for standard applications || 75 hp 575 V for severe applications
- Device Short Name
- ATS48
- Supply Frequency
- 50...60 Hz - 5...5 %
Contractual warranty
- Warranty
- 18 months
Complementary
- Product Certifications
- GOST || TCF || CCC || SEPRO || NOM 117 || C-tick || CSA || UL || DNV
- Device Connection
- in the motor supply line
- Height
- 290 mm
- Standards
- EN/IEC 60947-4-2
- Analogue Output Type
- current output AO 0-20 mA or 4-20 mA 500 Ohm
- Marking
- CE
- Net Weight
- 8.3 kg
- Connector Type
- 1 RJ45
- Communication Data Link
- serial
- Function Available
- external bypass (optional)
- Discrete Output Number
- 2
- Communication Port Protocol
- Modbus
- Discrete Input Type
- PTC, 750 Ohm 25 °C || Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
- Minimum Switching Current
- 10 mA 6 V DC relay outputs
- Physical Interface
- RS485 multidrop
- Discrete Input Number
- 5
- Operating Position
- vertical +/- 10 degree
- Width
- 190 mm
- Transmission Rate
- 4800, 9600 or 19200 bps
- Depth
- 235 mm
- Discrete Input Logic
- positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
- Protection Type
- phase failure line || thermal protection motor || thermal protection starter
- Discrete Output Type
- LO1) logic output 0 V common configurable || LO2) logic output 0 V common configurable || R1) relay outputs fault relay NO || R2) relay outputs end of starting relay NO || R3) relay outputs motor powered NO
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP111031EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI111007EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Environment
- Electromagnetic Compatibility
- conducted and radiated emissions level A IEC 60947-4-2 || conducted and radiated emissions level B IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-2 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 || voltage/current impulse level 3 IEC 61000-4-5
- Ambient Air Temperature For Operation
- 40-60 °C with current derating of 2 % per °C) || -10-40 °C without derating)
- Ambient Air Temperature For Storage
- -25-70 °C
- Relative Humidity
- 0-95 % without condensation or dripping water EN/IEC 60068-2-3
- Operating Altitude
- <= 3280.84 ft (1000 m) without derating || > 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional 100 m