Description

Active Mature
This Altivar Process ATV900 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It is suitable for motors with power rating up to 75kW/100HP for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 55kW/75HP for applications requiring significant overload (up to 150%). It works at a rated supply voltage from 380Vac to 480Vac. This variable speed / frequency drive (VSD / VFD) is specifically designed for industrial processes. In the following market segments, oil and gas, mining, minerals and metals, food and beverage water and wastewater. It offers high motor performance on any motor and total control of any kind of coupling in master/slave applications. Network services help ensure operation continuity even in case of connection breakdown. Web server and data logging help reduce downtime through fast troubleshooting and preventive maintenance. Its advanced connectivity, including EtherNet/IP and Modbus TCP, allows deep integration into automation architectures.
Country of Origin
IN
Part Number
ATV930D75N4C
Tariff Code
85044095
EAN
3606480883439
UNSPSC
39122001
Payment methods:
Best offer from:
ITTrusted Automa.Net Supplier
Availability:
8 pcs.
In-Stock
Updated at: 22-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Complementary

Discrete Input Logic
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V || positive logic (source) DI7, DI8), < 0.6 V, > 2.5 V || positive logic (source) STOA, STOB), < 5 V, > 11 V
Power Dissipation In W
natural convection 174 W 380 V 2.5 kHz || forced convection 1369 W 380 V 2.5 kHz
Analogue Output Type
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Discrete Output Type
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
Maximum Switching Current
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R3 resistive, cos phi = 1 5 A 250 V AC || relay output R2, R3 resistive, cos phi = 1 5 A 30 V DC || relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
Exchange Mode
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Local Signalling
local diagnostic 3 LED mono/dual colour) || embedded communication status 5 LED dual colour) || communication module status 2 LED dual colour) || presence of voltage 1 LED red)
Data Format
8 bits, configurable odd, even or no parity Modbus serial
Relative Symmetric Network Frequency Tolerance
5 %
Net Weight
58 kg
Type Of Polarization
no impedance
Relay Output Type
configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 1000000 cycles || configurable relay logic R3 sequence relay NO 1000000 cycles
Analogue Input Number
3
Motor Slip Compensation
can be suppressed || adjustable || automatic whatever the load || not available in permanent magnet motor law
Discrete Output Number
2
Transmission Rate
10/100 Mbit/s Ethernet IP/Modbus TCP || 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
Method Of Access
slave Modbus TCP
Number Of Addresses
1-247
Discrete Input Number
10
Linearity Error
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Number Of Addresses
1-247 Modbus serial
With Safety Function Safe Stop 1 (Ss1)
true
Width
290 mm
Transmission Rate
10, 100 Mbits || 4.8 kbps || 9600 bit/s || 19200 bit/s
Depth
325.5 mm
Analogue Input Type
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Sampling Duration
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
Electrical Connection
control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 || DC bus screw terminal 70...120 mm² AWG 1/0...250 kcmil || line side screw terminal 95...120 mm² AWG 3/0...250 kcmil || motor screw terminal 95...120 mm² AWG 3/0...250 kcmil
With Safety Function Safe Brake Management (Sbc/Sbt)
true
Height
922 mm
Acceleration And Deceleration Ramps
linear adjustable separately from 0.01...9999 s
Maximum Output Voltage
480.0 V
Base Load Current At High Overload
106.0 A
Transmission Frame
RTU
Relay Output Number
3
With Safety Function Safe Torque Off (Sto)
true
Data Format
8 bits, configurable odd, even or no parity
Base Load Current At Low Overload
145.0 A
Accuracy
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
Input Compatibility
DI1...DI8 discrete input level 1 PLC IEC 61131-2 || DI7, DI8 pulse input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
Connector Type
2 RJ45 || 1 RJ45
Analogue Output Number
2
Physical Interface
Ethernet || 2-wire RS 485
Minimum Switching Current
relay output R1, R2, R3 5 mA 24 V DC
Refresh Time
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Isolation
between power and control terminals
Quantity Per Set
1
Type Of Polarization
no impedance Modbus serial
Braking To Standstill
by DC injection
Discrete Input Type
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
Protection Type
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || motor phase break drive || overvoltages on the DC bus drive || line supply overvoltage drive || line supply undervoltage drive || line supply phase loss drive || overspeed drive || break on the control circuit drive
Supply
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
With Safety Function Safely Limited Speed (Sls)
true

Specifications

Prospective Line Isc
50 kA
Network Frequency
50-60 Hz
Product Destination
asynchronous motors || synchronous motors
Line Current
131.3 A 380 V normal duty) || 98.9 A 380 V heavy duty) || 112.7 A 480 V normal duty) || 86.9 A 480 V heavy duty)
Phase
3 phase
Asynchronous Motor Control Profile
optimized torque mode || variable torque standard || constant torque standard
Variant
standard version || without braking chopper
Product Or Component Type
variable speed drive
Apparent Power
93.7 kVA 480 V normal duty) || 72.2 kVA 480 V heavy duty)
Ip Degree Of Protection
IP21
Switching Frequency
1...8 kHz adjustable || 2.5...8 kHz with derating factor
Maximum Transient Current
174 A 60 s normal duty) || 159 A 60 s heavy duty)
Communication Port Protocol
Modbus TCP || Modbus serial || EtherNet/IP
Product Specific Application
process for industrial
Option Card
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module CANopen SUB-D 9 || slot A communication module CANopen screw terminals || slot A/slot B/slot C digital and analog I/O extension module || slot A/slot B/slot C output relay extension module || slot B 5/12 V digital encoder interface module || slot B analog encoder interface module || slot B resolver encoder interface module || communication module Ethernet Powerlink
Degree Of Protection
UL type 1
Maximum Output Frequency
599 Hz
Range Of Product
Altivar Process ATV900
Motor Power Kw
75.0 kW normal duty || 55.0 kW heavy duty
[Us] Rated Supply Voltage
380...480 V - 15...10 %
Mounting Mode
wall mount
Discrete Input Logic
16 preset speeds
Continuous Output Current
145 A 2.5 kHz normal duty || 106 A 2.5 kHz heavy duty
Nominal Switching Frequency
2.5 kHz
Emc Filter
integrated || with EMC plate option
Device Application
Industrial Application
Synchronous Motor Control Profile
permanent magnet motor || synchronous reluctance motor

Environment

Product Certifications
TÜV || UL || CSA
Maximum Deflection Under Vibratory Load (During Operation)
1.5 mm at 2...13 Hz
Standards
UL 508C || IEC 61800-3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Insulation Resistance
> 1 MOhm 500 V DC for 1 minute to earth
Shock Resistance
15 gn 11 ms IEC 60068-2-27
Environmental Characteristic
chemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
Vibration Resistance
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Noise Level
68.3 dB 86/188/EEC
Regulation Loop
adjustable PID regulator
Permitted Relative Humidity (During Operation)
class 3K5 according to EN 60721-3
Operating Altitude
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Overvoltage Category
III
Environmental Class (During Operation)
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
Maximum Acceleration Under Shock Impact (During Operation)
150 m/s² at 11 ms
Pollution Degree
2
Electromagnetic Compatibility
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency immunity test level 3 IEC 61000-4-6
Ambient Air Temperature For Operation
-15-50 °C without derating) || 50-60 °C with derating factor)
Volume Of Cooling Air
295 m3/h
Marking
CE
Maximum Acceleration Under Vibrational Stress (During Operation)
10 m/s² at 13...200 Hz
Noise Level
68.3 dB
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
5-95 % without condensation IEC 60068-2-3
Assembly Style
enclosed
Operating Position
vertical +/- 10 degree
Maximum Thdi
<48 % from 80...100 % of load IEC 61000-3-12
Ambient Air Transport Temperature
-40-70 °C

Offer Sustainability

Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Upgradeability
Upgraded components available
Rohs Exemption Information
Yes
Environmental Disclosure
ENVPEP1411014EN
Sustainable Offer Status
Green Premium product
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity Profile
ENVEOLI1411014EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)