- Mtbf Reliability
- 450000 H
- Voltage Range
- 21.1...29.0 V 70 °C || 19...30 V 60 °C
- Maximum Current Per Module
- 5 A 60 °C || 4.4 A 70 °C
- Switching Frequency
- 0.5/LI² Hz
- Maximum Overload Time
- 15 ms
- Status Led
- 1 LED (Green) module operating (RUN) || 1 LED per channel (Green) channel diagnostic || 1 LED (Red) module error (ERR) || 1 LED (Red) module I/O
- Voltage Detection Threshold
- < 14 V DC preactuator fault || < 14 V DC sensor fault || > 18 V DC preactuator OK || > 18 V DC sensor OK
- Current Per Channel
- 0.55 A 70 °C || 0.625 A 60 °C
- Maximum Voltage Drop
- <1.2 V at state 1
- Current Consumption
- <= 111 mA 3.3 V DC || <= 67 mA 24 V DC
- Insulation Resistance
- > 10 MOhm 500 V DC
- Current State 1 Guaranteed
- >= 3 mA
- Protection Type
- 1 external fuse per group of input channel 0.5 A fast blow || overvoltage protection on output || reverse polarity protection on input || reverse polarity protection on output
- Power Dissipation In W
- 3.7 W
- Net Weight
- 0.115 kg
- Maximum Leakage Current
- 0.5 mA at state 0
- Load Impedance Ohmic
- >= 48 Ohm
- Paralleling Of Outputs
- yes : 2 maximum
- Dc Typical Filtering Time
- 4 ms
- Input Compatibility
- with 2-wire/3-wire proximity sensors IEC 60947-5-2 || with 2-wire/3-wire proximity sensors IEC 61131-2 type 3
- Typical Current Consumption
- 79 mA 3.3 V DC || 59 mA 24 V DC
- Current State 0 Guaranteed
- <= 1.5 mA
- Output Overvoltage Protection
- with transil diode
- Output Short-Circuit Protection
- with 2 A external fuse
- Output Overload Protection
- with electronic circuit breaker 1.5 In < Id < 2 In || with current limiter
- Input Impedance
- 6800 Ohm
- Maximum Tungsten Load
- 6 W
- Reverse Polarity Protection
- reverse mounted diode
- Dc Maximum Filtering Time
- 7 ms
- Response Time On Output
- 1.2 ms