Schneider Electric
BMXP341000
processor, Modicon M340, max 512 discrete, 128 analog IO, Modbus
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€254.70
1
Payment methods:
A total of 294 Parts In-Stock from 47 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€212.33
Additional Information
- Part Number
- BMXP341000
- UNSPSC
- 32151707
- Tariff Code
- 8537109160
- Country of Origin
- FR
Environment
- Ambient Air Temperature For Operation
- 0-60 °C
- Standards
- EN 61131-2 || EN/IEC 61010-2-201 || UL 61010-2-201 || CSA C22.2 No 61010-2-201 || IACS E10 || EN/IEC 61000-6-5, interface type 1 and type 2 || EN/IEC 61850-3, location G
- Product Certifications
- CE || UL || CSA || RCM || EAC || Merchant Navy
- Environmental Characteristic
- hazardous location class I division 2
- Directives
- 2014/35/EU - low voltage directive || 2014/30/EU - electromagnetic compatibility
- Relative Humidity
- 10-95 % without condensation
- Protective Treatment
- TC
- Ip Degree Of Protection
- IP20
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Number Of Devices Per Segment
- 0-32 character mode) || 0-32 Modbus)
- Integrated Connection Type
- non isolated serial link RJ45 character mode asynchronous in baseband, RS232C 2 twisted shielded pairs 0.3...19.2 kbit/s full duplex || non isolated serial link RJ45 character mode asynchronous in baseband, RS485 1 twisted shielded pair 0.3...19.2 kbit/s half duplex || non isolated serial link RJ45, master/slave Modbus, RTU/ASCII asynchronous in baseband, RS232C 1 twisted shielded pair 0.3...19.2 kbit/s half duplex || non isolated serial link RJ45, master/slave Modbus, RTU/ASCII asynchronous in baseband, RS485 1 twisted shielded pair 0.3...19.2 kbit/s half duplex || USB port 12 Mbit/s
- Status Led
- 1 LED (Green) processor running (RUN) || 1 LED (Red) I/O module fault (I/O) || 1 LED (Red) memory card fault (CARD ERR) || 1 LED (Red) processor or system fault (ERR) || 1 LED (Yellow) activity on Modbus (SER COM)
- Communication Module Processor Capacity
- 2 Ethernet communication module || 2 AS-Interface module
- Requests
- 1 K data bytes per request character mode || 252 data bytes per RTU request Modbus || 504 data bytes per ASCII request Modbus
- Supply
- internal power supply via rack
- Default Size Of Object Areas
- 128 %KWi constant words located internal data || 256 %Mi located internal bits || 512 %MWi internal words located internal data
- Marking
- CE
- Current Consumption
- 72 mA 24 V DC
- Net Weight
- 0.2 kg
- Application Structure
- 1 periodic fast task || 32 event tasks || 1 cyclic/periodic master task || no auxiliary task
- System Overhead
- 0.2 ms fast task || 1.05 ms master task
- Maximum Size Of Object Areas
- 128 kB unlocated internal data || 16250 %Mi located internal bits || 32464 %MWi internal words located internal data || 32760 %KWi constant words located internal data
- Maximum Tap Links Length
- <15 m serial link non isolated character mode segment || <15 m serial link non isolated Modbus segment || <40 m serial link isolated character mode segment || <40 m serial link isolated Modbus segment
- Number Of Devices
- 2 point-to-point character mode || 2 point-to-point Modbus
- Execution Time Per Instruction
- 0.18 µs Boolean || 0.26 µs double-length words || 0.38 µs single-length words || 1.74 µs floating points
- Control Parameter
- one CRC on each frame (RTU) Modbus || one LRC on each frame (ASCII) character mode || one LRC on each frame (ASCII) Modbus
- Number Of Addresses
- 0-248 character mode || 0-248 Modbus
- Number Of Instructions Per Ms
- 4.2 Kinst/ms 65 % Boolean + 35 % fixed arithmetic || 5.4 Kinst/ms 100 % Boolean
- Bus Length
- 0-10 m serial link non isolated character mode segment || 0-10 m serial link non isolated Modbus segment || 0-1000 m serial link isolated character mode segment || 0-1000 m serial link isolated Modbus segment || 0-15 m character mode point-to-point || 0-15 m Modbus point-to-point
- Memory Description
- internal RAM 2048 kB || internal RAM 128 kB data || internal RAM 1792 kB program constants and symbols || supplied memory card (BMXRMS008MP) backup of programs, constants, symbols and data
- Control Channels
- programmable loops
Specifications
- Range Of Product
- Modicon M340 automation platform
- Number Of Racks
- 2
- Product Or Component Type
- processor module
- Analogue I/O Processor Capacity
- 66 I/O single-rack configuration || 128 I/O multi-rack configuration
- Number Of Slots
- 11
- Monitoring
- diagnostic counters Modbus || event counters Modbus
- Number Of Application Specific Channel
- 20
- Discrete I/O Processor Capacity
- 512 I/O single-rack configuration
Documents
Data Sheet
DownloadCAD Models
traceparts
Download