Schneider Electric
LAD8N20
TeSys Deca, auxiliary contact block, 2 NO, side mount, screw clamp terminals, for LC1D09 to LC1D150 contactors
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€7.00
1
Payment methods:
A total of 1,276 Parts In-Stock from 42 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€4.54
Additional Information
- Part Number
- LAD8N20
- UNSPSC
- 39121522
- Tariff Code
- 8536509065
- Country of Origin
- ID
Environment
- Ambient Air Temperature For Operation
- -5-60 °C
- Ip Degree Of Protection
- IP20 conforming to IEC 60529
- Ambient Air Temperature For Storage
- -60-80 °C
- Environmental Characteristic
- normal environment
- Protective Treatment
- TH IEC 60068
- Operating Altitude
- 9842.52 ft (3000 m)
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP110807EN_V3
- Sustainable Offer Status
- Green Premium product
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- Non-Overlap Time
- 1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
- Permissible Short-Time Rating
- 100 A 1 s || 120 A 500 ms || 140 A 100 ms
- Minimum Switching Current
- 5 mA
- Height
- 76 mm
- Protection Type
- gG fuse 10 A
- Insulation Resistance
- > 10 MOhm
- Irms Rated Making Capacity
- 140 A AC conforming to IEC 60947-5-1 || 250 A DC conforming to IEC 60947-5-1
- Connections - Terminals
- screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²rigid without cable end || screw clamp terminals 2 1-4 mm²rigid without cable end
- Minimum Switching Voltage
- 17 V
- Tightening Torque
- 1.7 N.m flat Ø 6 mm || 1.7 N.m Philips No 2 || 1.7 N.m pozidriv No 2
- Mechanical Durability
- 30 Mcycles
- Width
- 12.5 mm
- Depth
- 76 mm
Specifications
- Product Certifications
- CB || UL || CSA || CCC || EAC || UKCA
- [Ith] Conventional Free Air Thermal Current
- 10 A (at 60 °C)
- Standards
- EN/IEC 60947-5-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || EN 50012
- [Ue] Rated Operational Voltage
- 690 V AC 25...400 Hz
- Range Compatibility
- TeSys Deca LC1D09…95 AC coil || TeSys Deca LC1D40A…80A AC Coil || TeSys Deca LC1D115/150 || TeSys Deca CAD AC coil || TeSys F LC1F
- Product Or Component Type
- auxiliary contact block
- Product Name
- TeSys Deca
- Range
- TeSys
- Mounting Location
- side
- Pole Contact Composition
- 2 NO
- [Ui] Rated Insulation Voltage
- 690 V IEC 60947-5-1 || 600 V UL || 600 V CSA
- [Ie] Rated Operational Current
- 6 A at 120 V AC-15 || 1.04 A at 690 V AC-15 || 0.55 A at 125 V DC-13 || 0.1 A at 600 V DC-13
- Auxiliary Contacts Operation
- instantaneous
Documents