- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
- Minimum Switching Current
- 5 mA for control circuit
- Power Dissipation Per Pole
- 5.4 W AC-1
- Average Impedance
- 1.5 mOhm - Ith 60 A 50 Hz for power circuit
- [Ith] Conventional Free Air Thermal Current
- 10 A (at 60 °C) for control circuit || 60 A (at 60 °C) for power circuit
- Control Circuit Voltage Limits
- 0.3...0.6 Uc 60-60 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc 60-60 °C operational AC 50 Hz || 0.85...1.1 Uc 60-60 °C operational AC 60 Hz
- Mounting Support
- plate || rail
- Control Circuit Type
- AC 50/60 Hz standard
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Insulation Resistance
- > 10 MOhm for control circuit
- Rated Breaking Capacity
- 800 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 140 A AC for control circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating
- 10 A gG for control circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- Inrush Power In Va
- 140-140 VA cos phi 0.75 (at 20 °C) || 160-160 VA cos phi 0.75 (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Pole Contact Composition
- 4 NO
- Connections - Terminals
- control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminal 1 1-35 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminal 2 1-25 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminal 2 1-35 mm² - cable stiffness: solid without cable end
- Coil Technology
- without built-in bidirectional peak limiting diode suppressor
- Operating Time
- 12...26 ms closing || 4...19 ms opening
- Minimum Switching Voltage
- 17 V for control circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw clamp terminal flat Ø 6 mm || power circuit 5 N.m screw clamp terminal flat Ø 8 mm
- Mechanical Durability
- 6000000 cycles
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 13-13 VA 60 Hz cos phi 0.3 (at 20 °C) || 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
- Overvoltage Category
- III
- [Ui] Rated Insulation Voltage
- control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
- Heat Dissipation
- 4-5 W at 50/60 Hz for control circuit
- Protective Cover
- with