- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA for signalling circuit
- Power Dissipation Per Pole
- 9.6 W AC-1 || 3.7 W AC-3 || 3.7 W AC-3e
- Average Impedance
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 80 A (at 60 °C) for power circuit || 10 A (at 60 °C) for signalling circuit
- Control Circuit Voltage Limits
- <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC/DC || 1...1.1 Uc 60-70 °C operational AC/DC
- Mounting Support
- rail || plate
- Control Circuit Type
- AC/DC 50/60 Hz AC/DC electronic
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Hold-In Power Consumption In W
- 1.2-1.2 W 20 °C
- Insulation Resistance
- > 10 MOhm for signalling circuit
- Rated Breaking Capacity
- 900 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 900 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
- Associated Fuse Rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
- Inrush Power In Va
- 18-18 VA 50/60 Hz (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible without cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible without cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid
- Coil Technology
- built-in bidirectional peak limiting
- Operating Time
- 55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
- Minimum Switching Voltage
- 17 V for signalling circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Signalling Circuit Frequency
- 25...400 Hz
- Tightening Torque
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || power circuit 5 N.m pozidriv No 2 || control circuit 1.7 N.m pozidriv No 2
- Electrical Durability
- 1.8 Mcycles 42 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1.8 Mcycles 42 A AC-3e <= 440 V
- Mechanical Durability
- 6 Mcycles
- Inrush Power In W
- 14-14 W 20 °C)
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 1.8-1.8 VA 50/60 Hz (at 20 °C)
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 3 hp at 115 V AC 60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 1 phase motors || 15 hp at 200/208 V AC 60 Hz for 3 phase motors || 15 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 40 hp at 575/600 V AC 60 Hz for 3 phase motors
- Motor Power Kw
- 15 kW at 220...230 V AC 50 Hz (AC-3) || 22 kW at 380...400 V AC 50 Hz (AC-3) || 25 kW at 415 V AC 50 Hz (AC-3) || 30 kW at 440 V AC 50 Hz (AC-3) || 30 kW at 500 V AC 50 Hz (AC-3) || 33 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 220...230 V AC 50 Hz (AC-3e) || 22 kW at 380...400 V AC 50 Hz (AC-3e) || 25 kW at 415 V AC 50 Hz (AC-3e) || 30 kW at 440 V AC 50 Hz (AC-3e) || 30 kW at 500 V AC 50 Hz (AC-3e) || 33 kW at 660...690 V AC 50 Hz (AC-3e)
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
- [Icw] Rated Short-Time Withstand Current
- 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit || 84 A 40 °C - 10 min for power circuit || 208 A 40 °C - 1 min for power circuit || 400 A 40 °C - 10 s for power circuit || 810 A 40 °C - 1 s for power circuit
- Heat Dissipation
- 1.2-1.2 W at 50/60 Hz
- Protective Cover
- with