- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA signalling circuit
- Power Dissipation Per Pole
- 9.6 W AC-1 || 6.5 W AC-3 || 6.5 W AC-3e
- Average Impedance
- 1.5 mOhm - Ith 80 A 50 Hz power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
- Control Circuit Voltage Limits
- 0.3...0.6 Uc -40-70 °C drop-out AC 60 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 60 Hz
- Mounting Support
- rail || plate
- Contact Compatibility
- M2
- Control Circuit Type
- AC 60 Hz
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Insulation Resistance
- > 10 MOhm signalling circuit
- Rated Breaking Capacity
- 1000 A 440 V power circuit IEC 60947
- Irms Rated Making Capacity
- 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1000 A 440 V AC power circuit IEC 60947
- Associated Fuse Rating
- 10 A gG signalling circuit IEC 60947-5-1 || 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Inrush Power In Va
- 140-140 VA 60 Hz 0.75 20 °C)
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- power circuit EverLink BTR screw connectors 1 1-35 mm² flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm² flexible with cable end || control circuit spring terminals 1 0.75-2.5 mm² flexible without cable end || control circuit spring terminals 2 0.75-2.5 mm² flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm² solid || power circuit EverLink BTR screw connectors 2 1-25 mm² solid || power circuit EverLink BTR screw connectors 1 1-35 mm² flexible || power circuit EverLink BTR screw connectors 2 1-25 mm² flexible
- Coil Technology
- without built-in suppressor module
- Operating Time
- 4...19 ms opening || 12...26 ms closing
- Minimum Switching Voltage
- 17 V signalling circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Signalling Circuit Frequency
- 25...400 Hz
- Tightening Torque
- power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
- Electrical Durability
- 0.7 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3 <= 440 V || 1 Mcycles 66 A AC-3e <= 440 V
- Mechanical Durability
- 6 Mcycles
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 13-13 VA 60 Hz 0.3 20 °C)
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 5 hp 115 V at AC 60 Hz for 1 phase || 10 hp 230/240 V at AC 60 Hz for 1 phase || 20 hp 200/208 V at AC 60 Hz for 3 phase || 20 hp 230/240 V at AC 60 Hz for 3 phase || 40 hp 460/480 V at AC 60 Hz for 3 phase || 50 hp 575/600 V at AC 60 Hz for 3 phase
- Motor Power Kw
- 18.5 kW 220...230 V AC 50 Hz AC-3) || 37 kW 380...400 V AC 50 Hz AC-3) || 37 kW 415 V AC 50 Hz AC-3) || 37 kW 440 V AC 50 Hz AC-3) || 37 kW 500 V AC 50 Hz AC-3) || 37 kW 660...690 V AC 50 Hz AC-3)
- [Ui] Rated Insulation Voltage
- signalling circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-4-1
- [Icw] Rated Short-Time Withstand Current
- 520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
- Heat Dissipation
- 4-5 W 60 Hz
- Protective Cover
- with