1 / 1
thumbnail

Description

Active Mature
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 125 VDC coil with transient suppressor module. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.17 inches deep. It weighs 4.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Country of Origin
CZ
Part Number
LP1D40008GD
Tariff Code
85364900
EAN
3389110200195
UNSPSC
39121529
Payment methods:
Best offer from:
DETrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 08-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Environment

Product Certifications
UL || CSA || CCC || EAC || UKCA || CB || DNV-GL || RINA || BV || LROS (Lloyds register of shipping)
Height
127 mm
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Net Weight
2.21 kg
Flame Retardance
V1 conforming to UL 94
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
85 mm
Depth
182 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C || 60-70 °C with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110205EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Power Dissipation Per Pole
5.4 W AC-1
Average Impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
[Ith] Conventional Free Air Thermal Current
60 A (at 60 °C) for power circuit
Control Circuit Voltage Limits
0.1...0.3 Uc -40-55 °C drop-out DC || 0.85...1.1 Uc -40-55 °C operational DC
Mounting Support
rail || plate
Contact Compatibility
M3
Control Circuit Type
DC DC standard
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree
3
Hold-In Power Consumption In W
22-22 W 20 °C
Rated Breaking Capacity
800 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
800 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating
80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Pole Contact Composition
2 NO + 2 NC
Connections - Terminals
power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: solid || power circuit: screw clamp terminals 2 2.5-16 mm² - cable stiffness: solid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid
Coil Technology
built-in bidirectional peak limiting diode suppressor
Time Constant
75 ms
Operating Time
4...19 ms opening || 12...26 ms closing
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 5 N.m screw clamp terminals 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2
Electrical Durability
1.4 Mcycles 60 A AC-1 <= 440 V
Mechanical Durability
10 Mcycles
Inrush Power In W
22-22 W 20 °C)
Compatibility Code
LP1D
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
[Icw] Rated Short-Time Withstand Current
72 A 40 °C - 10 min for power circuit || 165 A 40 °C - 1 min for power circuit || 320 A 40 °C - 10 s for power circuit || 720 A 40 °C - 1 s for power circuit
Protective Cover
without

Specifications

[Uc] Control Circuit Voltage
125 V DC
[Ue] Rated Operational Voltage
power circuit <= 1000 V AC 25...400 Hz
Range Of Product
TeSys Deca
Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1
[Ie] Rated Operational Current
60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Poles Description
4P
Device Short Name
LP1D