- Network Frequency
- 50/60 Hz
- [Ics] Rated Service Breaking Capacity
- 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 40 kA 100 % EN/IEC 60947-2 - <= 250 V DC
- Height
- 81 mm
- Contact Position Indicator
- yes
- Earth-Leakage Protection
- separate block
- Mounting Support
- DIN rail
- 9 Mm Pitches
- 8
- Limitation Class
- 3
- Net Weight
- 0.48 kg
- Wire Stripping Length
- 14 mm for top or bottom connection
- Control Type
- toggle
- Connections - Terminals
- tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
- [Ui] Rated Insulation Voltage
- 500 V AC 50/60 Hz EN/IEC 60947-2
- Mounting Mode
- clip-on
- Electrical Durability
- 10000 cycles
- Mechanical Durability
- 20000 cycles
- Local Signalling
- ON/OFF indication
- [Uimp] Rated Impulse Withstand Voltage
- 6 kVEN/IEC 60947-2
- Color
- Gray
- Width
- 72 mm
- Provision For Padlocking
- padlockable
- Depth
- 72 mm
- Tightening Torque
- 2-2 N.m top or bottom
- Magnetic Tripping Limit
- 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
- [Ue] Rated Operational Voltage
- 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 250 V DC