This Zelio Logic SR2 compact smart relay / programmable controller uses a supply voltage of 24V direct current. It has 12 inputs / outputs with screw-clamp terminals, has an integrated clock and LCD display. It has compact design, allowing installation on DIN rail. It also offers simple programming, display and diagnosing of malfunctions display and navigation buttons. Its simple ladder programming makes it adapted for non-specialists.
Country of Origin
FR
Part Number
SR2B121BD
Tariff Code
85371098
EAN
3389110547542
UNSPSC
39122331
Payment methods:
Best offer from:
ITTrusted Automa.Net Supplier
Availability:
145 pcs.
In-Stock
Updated at: 21-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
A total of 176 Parts In-Stock from 4 Distributors
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (3)

SR2B121BD product image
Schneider Electric

SR2B121BD

Condition:
New Factory Sealed
Available:
8 pcs.
In-Stock
Updated at: 21-11-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
SR2B121BD product image
Schneider Electric

SR2B121BD

Condition:
New Surplus
Available:
22 pcs.
In-Stock
Updated at: 21-11-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
1
£125.05
net
SR2B121BD product image
Schneider Electric

SR2B121BD

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 21-11-2024
Offer from:
USTrusted Automa.Net Supplier
Estimated Delivery:
On Request
1

Environment

Product Certifications
GL || CSA || UL || GOST || C-tick
Standards
IEC 61000-4-12 || IEC 61000-4-4 level 3 || IEC 61000-4-5 || IEC 61000-4-11 || IEC 61000-4-2 level 3 || IEC 60068-2-6 Fc || IEC 61000-4-6 level 3 || IEC 60068-2-27 Ea || IEC 61000-4-3
Disturbance Radiated/Conducted
class B EN 55022-11 group 1
Ambient Air Temperature For Operation
-20-40 °C in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 || -20-55 °C IEC 60068-2-1 and IEC 60068-2-2
Immunity To Microbreaks
1 ms
Environmental Characteristic
EMC directive IEC 61000-6-2 || EMC directive IEC 61000-6-3 || EMC directive IEC 61000-6-4 || EMC directive IEC 61131-2 zone B || low voltage directive IEC 61131-2
Ip Degree Of Protection
IP20 IEC 60529 terminal block) || IP40 IEC 60529 front panel)
Pollution Degree
2 IEC 61131-2
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
95-95 % without condensation or dripping water
Maximum Altitude Transport
3048 m
Operating Altitude
6561.68 ft (2000 m)

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP060406EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI0604006EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Contacts Type And Composition
NO relay output
Input Impedance
12 kOhm IB...IG used as analogue input circuit || 12 kOhm IB...IG used as discrete input circuit || 7.4 kOhm I1...IA and IH...IR discrete input circuit
Discrete Input Type
resistive
Number Of Outputs
4 relay
Analogue Input Range
0...10 V || 0...24 V
Conversion Error
+/- 5 % 25 °C analogue input circuit || +/- 6.2 % 55 °C analogue input circuit
Output Thermal Current
8 A for all 4 outputs relay output
Discrete Input Voltage
24 V DC
Number Or Control Scheme Lines
0-240 ladder || 0-500 FBD
Lsb Value
39 mV analogue input circuit
Backup Time
10 years 25 °C
Clock Drift
12 min/year 0-55 °C || 6 s/month 25-25 °C
Analogue Input Type
common mode
Discrete Input Current
4 mA
Current State 1 Guaranteed
>= 1.2 mA IB...IG used as discrete input circuit) || >= 2.2 mA I1...IA and IH...IR discrete input circuit)
Response Time
10 ms from state 0 to state 1)relay output || 5 ms from state 1 to state 0)relay output
Clock
with
Power Dissipation In W
3 W without extension
Local Display
with
Net Weight
0.25 kg
[Uimp] Rated Impulse Withstand Voltage
4 kV EN/IEC 60947-1 and EN/IEC 60664-1
Voltage State 0 Guaranteed
<= 5 V I1...IA and IH...IR discrete input circuit || <= 5 V IB...IG used as discrete input circuit
Output Voltage Limits
24...250 V AC relay output) || 5...30 V DC relay output)
Conversion Time
smart relay cycle time analogue input circuit
Electrical Durability
AC-12 500000 cycles 230 V, 1.5 A relay output IEC 60947-5-1 || AC-15 500000 cycles 230 V, 0.9 A relay output IEC 60947-5-1 || DC-12 500000 cycles 24 V, 1.5 A relay output IEC 60947-5-1 || DC-13 500000 cycles 24 V, 0.6 A relay output IEC 60947-5-1
Connections - Terminals
screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid || screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid || screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end
Analogue Input Number
4
Voltage State 1 Guaranteed
>= 15 V I1...IA and IH...IR discrete input circuit || >= 15 V IB...IG used as discrete input circuit
Input Compatibility
3-wire proximity sensors PNP discrete input
Current State 0 Guaranteed
<= 0.5 mA IB...IG used as discrete input circuit) || <= 0.75 mA I1...IA and IH...IR discrete input circuit)
Supply Voltage Limits
19.2-30 V
Operating Distance
10 m between stations, with screened cable (sensor not isolated) analogue input circuit
Overvoltage Category
III IEC 60664-1
Mechanical Durability
10000000 cycles relay output
Maximum Supply Current
100 mA without extension)
Tightening Torque
0.5 N.m
Temperature Probe Type
NTC 10k 25 °C || NTC 1000k 25 °C || KTY81 210/220/221/222/250 || Pt 500
Switching Capacity In Ma
>= 10 mA 12 V relay output)
Analogue Input Resolution
8 bits
Operating Rate In Hz
0.1 Hz at Ie)relay output || 10 Hz no load)relay output
Counting Frequency
1 kHz discrete input
Discrete Input Number
8 IEC 61131-2 Type 1
Cycle Time
6-90 ms
Reverse Polarity Protection
with
Maximum Permissible Voltage
30 V analogue input circuit
Repeat Accuracy
+/- 2 % 55 °C analogue input circuit
[Us] Rated Supply Voltage
24 V DC
Checks
program memory on each power up

Specifications

Range Of Product
Zelio Logic
Product Or Component Type
compact smart relay

CAD Models

traceparts
traceparts
Download