1 / 2
thumbnail
thumbnail

Description

Active Mature
This Schneider Electric Zelio Logic SR2 discovery pack compact smart relay / programmable controller uses a supply voltage of 24 volts direct current, has 20 inputs / outputs with screw-clamp terminals and has an integrated LCD display. This compact programmable relay discovery pack is ideal for discovering the Zelio Logic range of programmable smart relays. It has compact form-factor, allowing installation on DIN rail. It also offers simple programming, display and diagnosing of malfunctions display and navigation buttons. Discovery package includes one copy of Zelio Soft and one USB cable to connect the relay to your PC. Simple ladder programming, adapted for non-specialists. Discovery package, coming with Zelio Soft programming software, the simplest way to learn and use this relay. Built-in EEPROM flash memory for data backup up to 10 years, easy-to-recover after a power shortage or incident. The main application of this module is industry and building/service sector. This product is certified by C-Tick, GL, UL, CSA and GOST. It meets EN/IEC 60068-2-6 Fc and EN/IEC 61000-4-11 standards. Easy to use, Zelio Logic provides a real alternative solutions based on cabled logic or specific cards.
Country of Origin
FR
Part Number
SR2PACK2BD
Tariff Code
85371098
EAN
3389110549737
UNSPSC
39122331
Payment methods:
Best offer from:
ITTrusted Automa.Net Supplier
Availability:
5 pcs.
In-Stock
Updated at: 21-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Environment

Product Certifications
GOST || C-tick || UL || GL || CSA
Standards
IEC 61000-4-6 level 3 || IEC 61000-4-3 || IEC 60068-2-27 Ea || IEC 61000-4-11 || IEC 61000-4-12 || IEC 60068-2-6 Fc || IEC 61000-4-5 || IEC 61000-4-2 level 3 || IEC 61000-4-4 level 3
Disturbance Radiated/Conducted
class B EN 55022-11 group 1
Ambient Air Temperature For Operation
-20-40 °C in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 || -20-55 °C IEC 60068-2-1 and IEC 60068-2-2
Immunity To Microbreaks
1 ms
Environmental Characteristic
EMC directive IEC 61000-6-2 || EMC directive IEC 61000-6-3 || EMC directive IEC 61000-6-4 || EMC directive IEC 61131-2 zone B || low voltage directive IEC 61131-2
Ip Degree Of Protection
IP20 IEC 60529 terminal block) || IP40 IEC 60529 front panel)
Pollution Degree
2 IEC 61131-2
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
95-95 % without condensation or dripping water
Maximum Altitude Transport
3048 m
Operating Altitude
6561.68 ft (2000 m)

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP060406EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI0604006EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Contacts Type And Composition
NO relay output
Input Impedance
12 kOhm IB...IG used as analogue input circuit || 12 kOhm IB...IG used as discrete input circuit || 7.4 kOhm I1...IA and IH...IR discrete input circuit
Discrete Input Type
resistive
Analogue Input Range
0...10 V || 0...24 V
Conversion Error
+/- 5 % 25 °C analogue input circuit || +/- 6.2 % 55 °C analogue input circuit
Output Thermal Current
8 A for all 8 outputs relay output
Number Or Control Scheme Lines
120-120 ladder || 0-200 FBD
Lsb Value
39 mV analogue input circuit
Discrete Input Voltage
24 V DC
Backup Time
10 years 25 °C
Clock Drift
12 min/year 0-55 °C || 6 s/month 25-25 °C
Analogue Input Type
common mode
Discrete Input Current
4 mA
Current State 1 Guaranteed
>= 1.2 mA IB...IG used as discrete input circuit) || >= 2.2 mA I1...IA and IH...IR discrete input circuit)
Response Time
10 ms from state 0 to state 1)relay output || 5 ms from state 1 to state 0)relay output
Clock
without
Power Dissipation In W
6 W without extension
Local Display
with
Net Weight
0.7 kg
Input/Output Number
20
Voltage State 0 Guaranteed
<= 5 V I1...IA and IH...IR discrete input circuit || <= 5 V IB...IG used as discrete input circuit
Output Voltage Limits
24...250 V AC relay output) || 5...30 V DC relay output)
Conversion Time
smart relay cycle time analogue input circuit
Electrical Durability
AC-12 500000 cycles 230 V, 1.5 A relay output IEC 60947-5-1 || AC-15 500000 cycles 230 V, 0.9 A relay output IEC 60947-5-1 || DC-12 500000 cycles 24 V, 1.5 A relay output IEC 60947-5-1 || DC-13 500000 cycles 24 V, 0.6 A relay output IEC 60947-5-1
Analogue Input Number
2
Connections - Terminals
screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid || screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid || screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end
Voltage State 1 Guaranteed
>= 15 V I1...IA and IH...IR discrete input circuit || >= 15 V IB...IG used as discrete input circuit
Input Compatibility
3-wire proximity sensors PNP discrete input
Current State 0 Guaranteed
<= 0.5 mA IB...IG used as discrete input circuit)
Supply Voltage Limits
19.2-30 V
Operating Distance
10 m between stations, with screened cable (sensor not isolated) analogue input circuit
Overvoltage Category
III IEC 60664-1
Mechanical Durability
10000000 cycles relay output
Maximum Supply Current
100 mA without extension)
Tightening Torque
0.5 N.m
Temperature Probe Type
NTC 10k 25 °C || NTC 1000k 25 °C || KTY81 210/220/221/222/250 || Pt 500
Switching Capacity In Ma
>= 10 mA 12 V relay output)
Analogue Input Resolution
8 bits
[Uimp] Rated Impulse Withstand Voltage
4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
Operating Rate In Hz
0.1 Hz at Ie)relay output || 10 Hz no load)relay output
Counting Frequency
1 kHz discrete input
Cycle Time
6-90 ms
Kit Composition
SR2B201BD || cable PC SR2USB01 for connection to PC
Reverse Polarity Protection
with
Maximum Permissible Voltage
30 V analogue input circuit
Repeat Accuracy
+/- 2 % 55 °C analogue input circuit
[Us] Rated Supply Voltage
24 V
Checks
program memory on each power up

Specifications

Range Of Product
Zelio Logic
Number Of Outputs
8 relay
Product Or Component Type
compact discovery packs
Discrete Input Number
12 IEC 61131-2 Type 1