- Product Certifications
- cULus || CE || UKCA || RCM || EAC || cULus HazLoc
- Resistance To Conducted Disturbances
- 10 V 0.15...80 MHz IEC 61000-4-6 || 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
- Resistance To Electromagnetic Fields
- 10 V/m 80 MHz...1 GHz IEC 61000-4-3 || 3 V/m 1.4 GHz...2 GHz IEC 61000-4-3 || 1 V/m 2 GHz...3 GHz IEC 61000-4-3
- Standards
- IEC 61131-2
- Ambient Air Temperature For Operation
- -10-35 °C vertical installation || -10-55 °C horizontal installation
- Storage Altitude
- 0-3000 m
- Pollution Degree
- 2
- Shock Resistance
- 15 gn 11 ms
- Resistance To Magnetic Fields
- 30 A/m 50/60 Hz IEC 61000-4-8
- Vibration Resistance
- 3.5 mm 5-8.4 Hz DIN rail || 3 gn 8.4-150 Hz DIN rail || 3.5 mm 5-8.4 Hz panel || 3 gn 8.4-150 Hz panel
- Ambient Air Temperature For Storage
- -25-70 °C
- Relative Humidity
- 10-95 %, without condensation in operation) || 10-95 %, without condensation in storage)
- Surge Withstand
- 1 kV I/O common mode IEC 61000-4-5 DC
- Ip Degree Of Protection
- IP20 with protective cover in place
- Resistance To Electrostatic Discharge
- 8 kV in air IEC 61000-4-2 || 4 kV on contact IEC 61000-4-2
- Operating Altitude
- 0...6561.68 ft (0...2000 m)
- Resistance To Fast Transients
- 2 kV relay outputIEC 61000-4-4
- Electromagnetic Emission
- radiated emissions 40 dBμV/m QP class A 10 m)30-230 MHz IEC 55011 || radiated emissions 47 dBμV/m QP class A 10 m)230-1000 MHz IEC 55011