TeSys island voltage interface module, 100-690V / 47-63Hz. Connected to a TPRBC bus coupler it measures the mains voltages powering the loads. It provides the voltage values for power and energy calculation, calculates the RMS values and phase sequence. Voltage measurement range 100-690 V +/- 5 %, phase frequency measurement range 47-63 Hz +/- 1 Hz in single phase or 3-phase systems. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Country of Origin
ID
Part Number
TPRVM001
Tariff Code
90303370
EAN
3606489832889
UNSPSC
39121521
Payment methods:
Best offer from:
GBTrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 22-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Environment

Ambient Air Temperature For Operation
-10-60 °C
Shock Resistance
15 gn 11 ms) IEC 60068-2-27
Vibration Resistance
1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
Electromagnetic Compatibility
electrostatic discharge, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || line voltage circuit: fast transients immunity test, level 3, 2 kV, conforming to EN/IEC 61000-4-4 || line voltage circuit: surge immunity test (common mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
Pollution Degree
2
Ambient Air Temperature For Storage
-25-70 °C
Protective Treatment
TC
Relative Humidity
5-95 %
Ip Degree Of Protection
IP20
Operating Altitude
0...6561.68 ft (0...2000 m) without derating
Fire Resistance
960 °C UL 94

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1904009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1904009EN
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Mounting Mode
horizontal and vertical 35 mm symmetrical rail)
Current Consumption
2 mA
[Us] Rated Supply Voltage
24 V DC supplied by the bus coupler
Height
118 mm
Product Certifications
UL || CSA || EAC (pending)
Standards
IEC 61010-2-201 || UL 61010-2-201 || CSA C22.2 No 61010-2-201
Connections - Terminals
measuring input removable spring terminal block 3 0.2-2.5 mm² AWG 24...AWG 14)rigid || measuring input removable spring terminal block 3 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || measuring input removable spring terminal block 3 0.25-2.5 mm² AWG 22...AWG 14)flexible with cable end
Power Dissipation In W
0.5 W maximum
Net Weight
0.159 kg
Width
25 mm
Depth
114 mm

Specifications

[Ue] Rated Operational Voltage
690 V AC 47...63 Hz
Product Or Component Type
voltage interface module
Product Name
TeSys island
Range
TeSys
Device Presentation
monitoring of the mains voltage powering the island || reporting of the voltage to the bus coupler to enable power & energy monitoring
Metering Type
phase voltage 100...690 V || phase frequency 47...63 Hz || phase sequence
Measurement Accuracy
voltage +/- 5 %, || frequency +/- 1 Hz,
Product Compatibility
TPRBC bus coupler
Local Signalling
for DS (device status) 1 LED (green/red) || for VS (voltage status) 1 LED (green/red)
Function Of Module
monitoring of voltages in single phase systems L-N or L-L || monitoring of voltages in 3-phase systems without neutral N connection || calculation of RMS phase voltages, voltage phase sequence, fundamental frequency || identification of dip and swell events level and duration
Overvoltage Category
III
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 61010-1
[Ui] Rated Insulation Voltage
690 V IEC 61010-1
Device Short Name
TPRVM