Limit switch, Limit switches XC Standard, XCKD, steel roller plunger, 1NC+1 NO, snap, M16
XCKD2102P16
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€13.03
1
Payment methods:
A total of 25 Parts In-Stock from 13 Distributors
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price

Additional Information

Part Number
XCKD2102P16
UNSPSC
39122213
Tariff Code
8536509055
Country of Origin
FR

Specifications

Movement Of Operating Head
linear
Range Of Product
Telemecanique Limit switches XC Standard
Fixing Mode
by the body
Type Of Operator
spring return roller plunger metal
Sensor Design
compact form C CENELEC EN 50047
Product Or Component Type
limit switch
Head Material
zamak
Material
metal
Head Type
plunger head
Type Of Approach
lateral approach, 2 directions
Series Name
standard format
Contacts Type And Composition
1 NC + 1 NO
Body Type
fixed
Contact Operation
snap action
Body Material
zamak
Device Short Name
XCKD
Number Of Poles
2

Contractual warranty

Warranty
18 months

Complementary

Height
65-65 mm
Terminals Description Iso N°1
(21-22)NC || (13-14)NO
Short-Circuit Protection
10 A cartridge fuse gG
Electrical Connection
screw-clamp terminals 1 x 0.34...2 x 1.5 mm²
Cable Entry
1 entry tapped for M16 x 1.5 cable gland 4-8 mm
Net Weight
0.185 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60664 || 6 kV IEC 60947-1
Switch Actuation
by 30° cam
[Ui] Rated Insulation Voltage
300 VUL 508 || 500 V 3)IEC 60947-1 || 300 VCSA C22.2 No 14
Electrical Durability
5000000 cycles, DC-13, 120 V, 4 W 60 cyc/mn 0.5 , DC IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, 24 V, 10 W 60 cyc/mn 0.5 , DC IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, 48 V, 7 W 60 cyc/mn 0.5 , DC IEC 60947-5-1 appendix C
Positive Opening Minimum Force
36 N
Positive Opening
with
Contacts Insulation Form
Zb
Mechanical Durability
10000000 cycles
Maximum Actuation Speed
0.5 m/s
Minimum Force For Tripping
12 N
Contact Code Designation
A300, AC-15 (Ue = 240 V), Ie = 3 A 10 A EN 60947-5-1 || A300, AC-15 (Ue = 240 V), Ie = 3 A 10 A IEC 60947-5-1 appendix A || Q300, DC-13 (Ue = 250 V), Ie = 0.27 A EN 60947-5-1 || Q300, DC-13 (Ue = 250 V), Ie = 0.27 A IEC 60947-5-1 appendix A
Width
31 mm
Depth
30 mm
Repeat Accuracy
0.1 mm on the tripping points with 1 million operating cycles
Maximum Resistance Across Terminals
25 MOhm IEC 60255-7 category 3

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110614EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
CCC || UL || CSA
Ik Degree Of Protection
IK06 EN 50102
Ambient Air Temperature For Operation
-25-70 °C
Standards
IEC 60947-5-1 || CSA C22.2 No 14 || IEC 60204-1 || EN 60204-1 || UL 508 || EN 60947-5-1
Ip Degree Of Protection
IP66IEC 60529 || IP67IEC 60529
Shock Resistance
50 gn 11 ms IEC 60068-2-27
Vibration Resistance
25 gn 10-500 Hz)IEC 60068-2-6
Ambient Air Temperature For Storage
-40-70 °C
Electrical Shock Protection Class
class I IEC 61140 || class I NF C 20-030
Protective Treatment
TC

Documents

Data Sheet

Download