Schneider Electric

XCKJ50541H29

1 / 1
thumbnail

Description

Active Mature
This product is an industrial EN 50041 format limit switch with 1 entry tapped M20 x 1.5 for ISO cable gland. It features a metal fixed body and a rotary head, with a variable length thermoplastic roller lever. Contacts: 2-pole NC + NO, break before make, slow break. This limit switch is supplied for actuation from left and right. The XCKJ range offers the most robust heads in his category.
Country of Origin
FR
Part Number
XCKJ50541H29
Tariff Code
85365080
EAN
3389110514506
UNSPSC
39122213
Payment methods:
Best offer from:
GBTrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 21-10-2024
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
A total of 3 Parts In-Stock from 3 Distributors
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (2)

XCKJ50541H29 product image
Schneider Electric

XCKJ50541H29

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 22-11-2024
Offer from:
DETrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
XCKJ50541H29 product image
Schneider Electric

XCKJ50541H29

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 20-11-2024
Offer from:
FRTrusted Automa.Net Supplier
Estimated Delivery:
On Request
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Specifications

Movement Of Operating Head
rotary
Range Of Product
Telemecanique Limit switches XC Standard
Fixing Mode
by the body
Type Of Operator
spring return roller lever thermoplastic variable length
Cable Entry
1 entry tapped for M20 x 1.5 cable gland 7-13 mm
Product Or Component Type
limit switch
Head Material
zamak
Material
metal
Head Type
rotary head
Type Of Approach
lateral approach, 1 or 2 programmable direction
Series Name
standard format
Contacts Type And Composition
1 NC + 1 NO
Body Type
fixed
Contact Operation
slow-break, break before make
Body Material
zamak
Device Short Name
XCKJ
Number Of Poles
2

Contractual warranty

Warranty
18 months

Complementary

Height
77-77 mm
Terminals Description Iso N°1
(21-22)NC || (13-14)NO
Short-Circuit Protection
10 A cartridge fuse gG
Minimum Actuation Speed
6 m/min
Electrical Connection
screw-clamp terminals 1 x 0.5...2 x 2.5 mm²
Number Of Steps
1
[Ithe] Conventional Enclosed Thermal Current
10 A
Net Weight
0.485 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60664 || 6 kV IEC 60947-1
Switch Actuation
by 30° cam
[Ui] Rated Insulation Voltage
300 VUL 508 || 500 V 3)IEC 60947-1 || 300 VCSA C22.2 No 14
Electrical Durability
5000000 cycles, DC-13, inductive, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, inductive, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C || 5000000 cycles, DC-13, inductive, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Positive Opening
without
Contacts Insulation Form
Zb
[Ie] Rated Operational Current
3 A 240 V, AC-15, A300 EN/IEC 60947-5-1 appendix A || 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 appendix A
Mechanical Durability
30000000 cycles
Maximum Actuation Speed
1.5 m/s
Width
40 mm
Depth
44 mm
Minimum Torque For Tripping
0.25 N.m
Maximum Resistance Across Terminals
25 MOhm IEC 60255-7 category 3

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110614EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
UL || CSA || CCC
Ik Degree Of Protection
IK07 EN 50102
Ambient Air Temperature For Operation
-25-70 °C
Standards
CENELEC EN 50041 || IEC 60947-5-1 || UL 508 || EN 60947-5-1 || EN 60204-1 || IEC 60204-1 || CSA C22.2 No 14
Shock Resistance
50 gn 11 ms IEC 60068-2-27
Vibration Resistance
25 gn 10-500 Hz)IEC 60068-2-6
Ip Degree Of Protection
IP66 conforming to IEC 60529
Ambient Air Temperature For Storage
-40-70 °C
Overvoltage Category
class I IEC 61140 || class I NF C 20-030
Protective Treatment
TH