The XMLG range is an offer of electronic pressure transmitters, with an analogue or solid-state output. The XMLG transmitters feature a stainless steel AISI 303 body and a ceramic cell combined with a viton gasket. Therefore, they are compatible with industrial fluids such as air, fresh water and hydraulic oils. From 0bar to 400bar or 0psi to 5800psi. Analogue output: 4mA to 20mA. Fluid connection: G 1/4 A (male). Electrical connection: M12.- Country of Origin
- CH
- Part Number
- XMLG400D21
- Tariff Code
- 90262020
- EAN
- 3389110974072
- UNSPSC
- 39122210
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 1 pc.In-StockUpdated at: 21-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Specifications
- Pressure Sensor Type
- pressure transmitter
- Electrical Connection
- 1 male connector M12, 3 pins
- Type Of Output Signal
- analogue
- Diameter
- 22.8 mm
- Range Of Product
- Telemecanique Pressure sensors XM
- Product Or Component Type
- electronic pressure sensors
- Type Of Packing
- individual
- Pressure Sensor Name
- XMLG
- Fluid Connection Type
- G 1/4A (male) DIN 3852-E
- Pressure Sensor Size
- 400 bar
- Controlled Fluid
- air -15-125 °C) || corrosive fluid -15-125 °C) || hydraulic oil -15-125 °C) || fresh water 0-125 °C)
- Analogue Output Function
- 4...20 mA, 2 wires
- Quantity Per Set
- set of 1
- [Us] Rated Supply Voltage
- 12 V DC 8-33 V) || 24 V DC 8-33 V)
Contractual warranty
- Warranty
- 18 months
Complementary
- Height
- 58.1 mm
- Response Time On Output
- < 2 ms
- [Uimp] Rated Impulse Withstand Voltage
- 0.5 kV
- Repeat Accuracy
- +/- 0.1 % of the measuring range
- Drift Of The Zero Point
- +/- 0.015 % of measuring range/°C
- Materials In Contact With Fluid
- ceramic || FPM (Viton) || PPS || stainless steel type AISI 303
- Length
- 48.5 mm
- Local Display
- without
- Net Weight
- 0.095 kg
- Current Consumption
- < 20 mA
- Surge Withstand
- 1 kV 42 Ohm EN/IEC 61000-4-5 || 500 kV 12 Ohm EN/IEC 61000-4-5
- Scale Type
- fixed differential
- Mechanical Durability
- 10000000 cycles
- Operating Position
- any position
- Measurement Accuracy
- +/- 0.3 % of the measuring range
- Protection Type
- reverse polarity || load short-circuit
- Electrical Circuit Type
- control circuit
- Drift Of The Sensitivity
- +/- 0.015 % of measuring range/°C
- Maximum Permissible Accidental Pressure
- 800 bar
- Destruction Pressure
- 900 bar
- Pressure Setting Range
- 0-400 bar
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Environment
- Product Certifications
- UL 508 || EAC || CSA C22.2 No 14
- Resistance To Conducted Disturbances
- 30 V 0.15-80 Hz)EN/IEC 61000-4-6
- Ambient Air Temperature For Operation
- -15-85 °C
- Resistance To Electromagnetic Fields
- 200 V/m 80-1000 Hz EN/IEC 61000-4-3
- Standards
- EN/IEC 61326-2-3 || CE
- Shock Resistance
- 25 gn 11 ms EN/IEC 60068-2-27
- Resistance To Magnetic Fields
- 30 A/m 50 Hz EN/IEC 61000-4-8
- Vibration Resistance
- 20 gn 9-2000 Hz)EN/IEC 60028-2-6
- Ip Degree Of Protection
- IP66 conforming to EN/IEC 60529 || IP67 conforming to EN/IEC 60529
- Nema Degree Of Protection
- NEMA 4
- Ambient Air Temperature For Storage
- -40-85 °C
- Resistance To Electrostatic Discharge
- 15 kV in air EN/IEC 61000-4-2 || 8 kV on contact EN/IEC 61000-4-2
- Protective Treatment
- TC
- Resistance To Fast Transients
- 4 kV EN/IEC 61000-4-4