- [Us] Rated Supply Voltage
- 115 V AC - 15...15 %
- Range Of Product
- Preventa Safety automation
- Product Or Component Type
- Preventa safety module
- Safety Module Name
- XPSAC
- Type Of Start
- unmonitored
- Output Type
- relay instantaneous opening, 3 NO, volt-free
- Connections - Terminals
- captive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² flexible with cable end, with double bezel || captive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid with cable end, with double bezel || captive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezel || captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mm² solid with cable end, with double bezel || captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1.5 mm² flexible with cable end, with double bezel || captive screw clamp terminals, removable terminal block, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezel || captive screw clamp terminals, removable terminal block, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
- Number Of Additional Circuits
- 1 solid state output
- Safety Module Application
- for emergency stop and switch monitoring
- Safety Reliability Data
- MTTFd = 210.4 years EN/ISO 13849-1 || DC > 99 % EN/ISO 13849-1 || PFHd = 3.56E-9 1/h EN/IEC 62061
- Function Of Module
- switch monitoring || emergency stop
- Safety Level
- can reach PL e/category 4 EN/ISO 13849-1 || can reach SILCL 3 EN/IEC 62061