Wago

2006-1631/1000-836

1 / 2
thumbnail
thumbnail
Part Number
2006-1631/1000-836
Tariff Code
85369095000
UPC
4045454824044
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Fuse terminal block
Class Code : EC000899
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-3
Ratings (note)
Electrical ratings are given by the fuse and blown fuse indication.
Nominal voltage (III/3)
800 V
Rated impulse voltage (III/3)
8 kV
Rated current
10 A
Note (rated current)
Leakage current in case of a blown fuse: LED 2 mA
Operation status indicator
230 V
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
7.5 mm / 0.295 inches
Height
96.3 mm / 3.791 inches
Depth from upper-edge of DIN-rail
59 mm / 2.323 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.453 MJ
Weight
25.087 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

General

Fuse receptacle
Pivoting
Fuse type
Cylindrical fuse; 1/4" x 1 1/4"

Specifications

Product Group Code
0022

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4045454824044
Customs tariff number
85369095000

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
15 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
15 A

Power Loss

Power loss (max.) Pl (max.) (note)
When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN 60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
Power loss Pl max. overload and short-circuit protection (individual arrangement)
1.6 W
Power loss Pl max. overload and short-circuit protection (group arrangement)
1.6 W
Power loss Pl max. short-circuit protection (individual arrangement)
2.5 W
Power loss Pl max. short-circuit protection (group arrangement)
2.5 W

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
6 mm²
Solid conductor
0.5 … 10 mm² / 20 … 8 AWG
Solid conductor; push-in termination
1 … 10 mm² / 14 … 8 AWG
Fine-stranded conductor
0.5 … 10 mm² / 20 … 8 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 6 mm² / 20 … 10 AWG
Fine-stranded conductor; with ferrule; push-in termination
2.5 … 6 mm² / 16 … 10 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
13 … 15 mm / 0.51 … 0.59 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
230 V
Rated current UL (Use Group B)
15 A
Rated voltage UL (Use Group C)
230 V
Rated current UL (Use Group C)
15 A