Wago
2007-8801/046-000
1 / 2
- Part Number
- 2007-8801/046-000
- Tariff Code
- 85369010000
- UPC
- 4055143394840
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Feed-through terminal block
- Class Code : EC000897
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Ratings Per Iec/En
- Nominal voltage (III/3)
- 500 V
- Rated impulse voltage (III/3)
- 6 kV
- Rated current
- 30 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Processing temperature
- -35 … +85 °C
- Continuous operating temperature
- -60 … +105 °C
Physical Data
- Width
- 8 mm / 0.315 inches
- Height
- 99.6 mm / 3.921 inches
- Depth from upper-edge of DIN-rail
- 46.8 mm / 1.843 inches
Material Data
- Note (material data)
- <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
- Color
- Gray
- Material group
- I
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 0.000 MJ
- Weight
- 22.003 g
- Test socket color
- Black
Mechanical Data
- Mounting type
- DIN-35 rail
- Marking level
- Center/side marking
Specifications
- Product Group Code
- 0022
Commercial Data
- Packaging type
- Box
- Country of origin
- CN
- GTIN
- 4055143394840
- Customs tariff number
- 85369010000
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group B)
- 300 V
- Rated current CSA (Use Group B)
- 30 A
- Rated voltage CSA (Use Group C)
- 300 V
- Rated current CSA (Use Group C)
- 30 A
- Rated voltage CSA (Use Group D)
- 300 V
- Rated current CSA (Use Group D)
- 10 A
Power Loss
- Power loss, per pole (potential)
- 0.702 W
- Rated current IN for specified power loss
- 30 A
- Resistance value for specified, current-dependent power loss
- 0.00078 Ω
Connection 1
- Connection technology
- Push-in CAGE CLAMP®
- Actuation type
- Operating tool
- Connectable conductor materials
- Copper
- Nominal cross-section
- 6 mm² / 10 AWG
- Solid conductor
- 0.5 … 10 mm² / 20 … 8 AWG
- Solid conductor; push-in termination
- 1 … 10 mm² / 14 … 8 AWG
- Fine-stranded conductor
- 0.5 … 10 mm² / 20 … 8 AWG
- Fine-stranded conductor; with insulated ferrule
- 0.5 … 6 mm² / 20 … 10 AWG
- Fine-stranded conductor; with uninsulated ferrule
- 1.5 … 6 mm² / 16 … 10 AWG
- Fine-stranded conductor; with ferrule; push-in termination
- 2.5 … 6 mm² / 16 … 10 AWG
- Strip length
- 13 … 15 mm / 0.51 … 0.59 inches
- Wiring direction
- Front-entry wiring
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 300 V
- Rated current UL (Use Group B)
- 30 A
- Rated voltage UL (Use Group C)
- 300 V
- Rated current UL (Use Group C)
- 30 A
- Rated voltage UL (Use Group D)
- 300 V
- Rated current UL (Use Group D)
- 10 A