Wago
2022-1802
1 / 2
- Part Number
- 2022-1802
- Tariff Code
- 85369010000
- UPC
- 4055143927116
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Feed-through terminal block
- Class Code : EC000897
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Ratings Per Iec/En
- Ratings per
- IEC/EN 60947-7-1
- Nominal voltage (III/3)
- 690 V
- Rated impulse voltage (III/3)
- 6 kV
- Rated current
- 24 A
- Current at conductor cross-section (max.) mm²
- 27 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Continuous operating temperature
- -60 … +105 °C
Connection Data
- Female plug slots
- 4
- Total number of potentials
- 1
- Number of levels
- 1
Physical Data
- Width
- 5.2 mm / 0.205 inches
- Height
- 106 mm / 4.173 inches
- Depth from upper-edge of DIN-rail
- 32.5 mm / 1.28 inches
Material Data
- Note (material data)
- Information on material specifications can be found here
- Color
- Orange
- Material group
- I
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 0.000 MJ
- Weight
- 11.758 g
Mechanical Data
- Design
- Horizontal type
- Mounting type
- DIN-35 rail
- Marking level
- Center/side marking
Specifications
- Product Group Code
- 0018
Commercial Data
- Packaging type
- Box
- Country of origin
- CN
- GTIN
- 4055143927116
- Customs tariff number
- 85369010000
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group C)
- 600 V
- Rated current CSA (Use Group C)
- 20 A
Power Loss
- Power loss, per pole (potential)
- 0.7661 W
- Rated current IN for specified power loss
- 24 A
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 600 V
- Rated current UL (Use Group B)
- 20 A
- Rated voltage UL (Use Group C)
- 600 V
- Rated current UL (Use Group C)
- 20 A