Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
800 V
Rated impulse voltage (III/3)
8 kV
Rated current
57 A
Current at conductor cross-section (max.) mm²
74 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
10 mm / 0.394 inches
Height
89 mm / 3.504 inches
Depth from upper-edge of DIN-rail
36.9 mm / 1.453 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.093 MJ
Weight
25.452 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

Connection 2

Actuation type 2
Operating tool

Specifications

Product Group Code
0035

Commercial Data

Packaging type
Box
Country of origin
PL
GTIN
4055143865180
Customs tariff number
85369010000

Ex Information

Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 19 ATEX 1017 U / IECEx: PTB 19.0047U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
550 V
Rated current (Ex e II)
57 A
Rated current (Ex e II) with jumper
50 A

Power Loss

Power loss, per pole (potential)
1.8194 W
Rated current IN for specified power loss
57 A
Resistance value for specified, current-dependent power loss
0.00056 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Lever
Connectable conductor materials
Copper
Nominal cross-section
10 mm²
Solid conductor
0.5 … 16 mm² / 20 … 6 AWG
Solid conductor; push-in termination
4 … 16 mm² / 14 … 6 AWG
Fine-stranded conductor
0.5 … 16 mm² / 20 … 6 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 10 mm² / 20 … 8 AWG
Fine-stranded conductor; with ferrule; push-in termination
4 … 10 mm² / 12 … 8 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
17 … 19 mm / 0.67 … 0.75 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
65 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
65 A