Wago

2202-1981/1000-449

1 / 1
thumbnail
Part Number
2202-1981/1000-449
Tariff Code
85369095000
UPC
4066966083088
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Fuse terminal block
Class Code : EC000899
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-3
Ratings (note)
Electrical ratings are given by the fuse and blown fuse indication.
Nominal voltage (III/3)
400 V
Rated impulse voltage (III/3)
6 kV
Rated current
10 A
Operation status indicator
12 V
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Ratings Per Iec/En 2

Ratings (note) 2
Blade-style fuses: Observe touch-proof protection for 42 V and higher voltages!10 A (individual arrangement)5 A (block arrangement)

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
5.2 mm / 0.205 inches
Height
72.9 mm / 2.87 inches
Depth from upper-edge of DIN-rail
32.9 mm / 1.295 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Gray
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.187 MJ
Weight
9.451 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

General

Fuse receptacle
Pluggable
Fuse type
Mini flat plug-in fuse; 10.9 x 3.6 x 16.3 mm

Specifications

Product Group Code
0036

Commercial Data

Country of origin
DE
GTIN
4066966083088
Customs tariff number
85369095000

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
12 V
Rated current CSA (Use Group B)
10 A
Rated voltage CSA (Use Group C)
12 V
Rated current CSA (Use Group C)
10 A

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Push-button
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm²
Solid conductor
0.25 … 4 mm² / 22 … 12 AWG
Solid conductor; push-in termination
0.75 … 4 mm² / 18 … 12 AWG
Fine-stranded conductor
0.25 … 4 mm² / 22 … 12 AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5 mm² / 18 … 14 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12 mm / 0.39 … 0.47 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
12 V
Rated current UL (Use Group B)
10 A
Rated voltage UL (Use Group C)
12 V
Rated current UL (Use Group C)
10 A

Related products