Wago

2222-1304/999-953

1 / 1
thumbnail
Part Number
2222-1304/999-953
Tariff Code
85366990990
UPC
4066966204209
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Feed-through terminal block
Class Code : EC000897
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Rated current
20 A

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
5.2 mm / 0.205 inches
Height
59.2 mm / 2.331 inches
Depth from upper-edge of DIN-rail
36.4 mm / 1.433 inches

Material Data

Note (material data)
Information on material data can be found here
Color
Blue
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.160 MJ
Weight
6.660 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

Specifications

Product Group Code
0018

Commercial Data

Country of origin
PL
GTIN
4066966204209
Customs tariff number
85366990990

Ex Information

Rated voltage EN (Ex e II)
630 V

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
20 A

Power Loss

Power loss, per pole (potential)
0.532 W
Rated current IN for specified power loss
20 A
Resistance value for specified, current-dependent power loss
0.00133 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Push-button
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm²
Solid conductor
0.25 … 4 mm² / 22 … 12 AWG
Solid conductor; push-in termination
0.75 … 4 mm² / 18 … 12 AWG
Fine-stranded conductor
0.25 … 4 mm² / 22 … 12 AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5 mm² / 22 … 14 AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5 mm² / 18 … 14 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12 mm / 0.39 … 0.47 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
20 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
20 A

Related products